Samson 2479 Mounting And Operating Instructions page 30

Differential pressure and temperature regulator with flow limitation
Table of Contents

Advertisement

Installation
Î Make sure the direction of flow matches
the direction indicated by the arrow on
the body.
Î Contact SAMSON if the mounting posi-
tion is not as specified above.
NOTICE
!
Damage due to freezing.
Protect the regulator from icing up when con-
trolling media that can freeze. Unless the
regulator is installed in locations where no
frost occurs, remove the regulator from the
pipeline when the plant is shut down.
Standard mounting position,
control thermostat
suspended to hand downward
All versions.
Alternative mounting position,
control thermostat on top
All versions, DN 15 to 25.
Maximum medium temperature
110 °C
Alternative mounting position,
vertical pipeline
All versions, DN 15 to 25.
Maximum medium temperature
110 °C
Fig. 5-1: Mounting position
5-2
Temperature sensor
NOTICE
!
Galvanic corrosion due to incorrectly se-
lected materials of the mounting parts.
On installing the sensor or thermowell, only
combine the same kind of materials (e.g.
stainless steel with stainless steel or copper
together with other copper materials).
The temperature sensor (25), even together
with a thermowell, can be installed in any
position as required. However, make sure its
entire length is immersed in the process me-
dium to be controlled. It must be installed in
a location where overheating or consider-
able idling times cannot occur.
Note
If the sensor is to be used with a thermowell,
only use original SAMSON thermowells.
Weld a welding socket with G ½ or G ¾ fe-
male thread (to match the screw gland) at
the place of installation.
Î Seal the screw gland of the sensor.
Installation with thermowell
When a thermowell is used, a welding sock-
et with G 1 female thread must be used.
1. Seal the thermowell into the welding
socket.
2. Insert the sensor and tighten it with the
clamping screw.
EB 3132-3 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

2430

Table of Contents