Mounting

Storage temperature
–40 to +80 °C (–40 to +176 °F)
Optional: –50 °C (–58 °F), –60 °C (–76 °F)
3.3.2
Transporting the device
• Transport the device to the measuring point in the original packaging
• Hold the device by the housing, temperature spacer, flange or extension pipe
• Do not bend, shorten or extend the tuning fork
 2
Handling the device during transportation
4
Mounting
WARNING
L
Loss of protection rating if the device is opened in a wet environment.
Only open the device in a dry environment!
Mounting instructions
• Any orientation for device with short pipe up to approx. 500 mm (19.7 in)
• Vertical orientation for device with long pipe
• Minimum distance between the fork tip and the tank wall or pipe wall: 10 mm (0.39 in)
8
Liquiphant FTL51B
A0034846
Endress+Hauser