5
1. Specify "CODE No." [14]
("CODE No." [14]: Group address)
2. Change the "SET DATA" from [0001] to [0002]
buttons.
("SET DATA" [Header unit: 0001] [Follower unit:
0002])
3. Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
Indoor "UNIT No." before setup change is displayed.
6
If there is other indoor unit to be changed,
repeat procedure
When the above setup has finished, push
to select the indoor "UNIT No." before change of
setup, specify "CODE No." [12], [13], [14] in order
with
buttons, and then check the changed
contents.
Address change check Before change:
[3-3-1] → After change: [2-2-2]
Pushing
button clears the contents of which
setup was changed.
(In this case, procedure from
Indoor "UNIT No." before setup change is displayed.
buttons.
2
5
to
to change the setup.
2
is repeated.)
7
After check of the changed contents, push
button. (Setup is determined.) When
button is pushed, the display disappears
and the status becomes the usual stop
status. (When
operation from the remote controller is not
accepted for approx. 1 minute.)
• If the operation from the remote controller is not
accepted even 1 minute or more passed after
pushing
button, it is considered that the
address setup is incorrect.
In this case, the automatic address must be
again set up.
Therefore repeat procedure of the setup
change from the Procedure
 Resetting the address
(Resetting to the factory default (address undecided))
Clearing each address separately using a wired
remote controller.
Set the system address, indoor unit address and group
address to [00Un] using a wired remote controller.
(For the setting procedure, refer to the address setting
procedures using the wired remote controller on the
previous pages.)