Lite-Vision plus Remote Controller Installation Manual Model name: RBC-AMS51E-ES RBC-AMS51E-EN • Read this manual before using the RBC- AMS51E-ES, RBC-AMS51E-EN remote controller. • Refer to the Installation Manual supplied with the indoor unit for any installation instructions other than operations of the remote controller.
Installation Manual Lite-Vision plus Remote Controller Precautions for Safety • Read these “Precautions for Safety” carefully before installation. • The precautions described below include important items regarding safety. Observe them without fail. Understand the following details (indications and symbols) before reading the body text, and follow the instructions.
Installation Manual Lite-Vision plus Remote Controller Installation Requirements to install the remote controller ◆ Installation place • Install the remote controller at a height of 1 to 1.5 m from the floor so that the average temperature in the room can be detected.
Page 6
Installation Manual Lite-Vision plus Remote Controller ◆ Remote control wiring and inter-unit wiring between remote controllers Do not allow the wire for the remote controller (communication wire) and the wire for AC220-240 V to come into contact or put them together in one electrical conduit; otherwise, the control system may have trouble due to noise. * Varies depending on the type of remote controller used.
Installation Manual Lite-Vision plus Remote Controller Install the remote controller NOTE • Wiring for the remote controller should not be bundled or installed in the same conduit with a power cable.; otherwise, malfunction may result. • Install the remote controller away from sources of electrical interference and electromagnetic fields. Wood screw x 2 Rear case Remote...
Installation Manual Lite-Vision plus Remote Controller Wire the remote controller Wiring diagram Terminal block for the remote control wiring on the indoor unit Remote control wiring (procured locally) Remote controller * Terminals of A and B Terminal block for have no polarity. the remote control wiring * Use wire of 0.5 mm...
Page 9
Installation Manual Lite-Vision plus Remote Controller Basic wiring diagram NOTE Terminals of A and B have no polarity. To diverge from the indoor unit To diverge from the header remote controller Remote controller Remote controller Remote controller Remote controller (header) (follower) (header) (follower)
Installation Manual Lite-Vision plus Remote Controller For first use It takes some time before the remote controller becomes operable when the remote controller is used for the first time. This is not a malfunction. <When the power is turned on for the first time after installation> It takes about 5 minutes before the remote controller becomes operable.
Installation Manual Lite-Vision plus Remote Controller Part Names and Functions Room A 12:00 Cool Mode Fan Speed Temperature sensor ON / OFF] button F1] button Varies its function according to the setting screen. ∧ ] button F2] button During normal operation: adjusts the temperature. On the menu screen: selects a menu item.
Installation Manual Lite-Vision plus Remote Controller Monitor screen Check the current usage status. Push [ MONITOR] button. Room A 12:00 The monitor screen appears. Push [ CANCEL] button to return. Cool Mode Fan Speed Monitor (1) Displays the set temperature. (2) Displays the temperature measured by the indoor Set temp.
Installation Manual Lite-Vision plus Remote Controller Initial setting Push the [ MENU] button to display the menu screen. Initial setting(1/2) 1.Clock ∧ ∨ 2.Name of room Push the [ ] / [ ] button to select 3.Screen contrast “10.Initial setting”on the menu screen, then 4.Backlight 5.Key lock push the “...
Installation Manual Lite-Vision plus Remote Controller To adjust the clock Clock ∧ ∨ Push the [ ] / [ ] button to select Date “1. Clock” on the “Initial setting” screen, Month then push the “ Set” [ Year 2010 button.
Installation Manual Lite-Vision plus Remote Controller B e d r o o “ Del ” and To delete a character, highlight ABCDE Z & / : · uvwxy push [ MENU] button. FGH I J abcde z–+!? KLMNO f g h i j 12345 PQRST klmno...
Installation Manual Lite-Vision plus Remote Controller 4. Backlight Turn on or off the back light of the LCD. Initial setting(1/2) ∧ ∨ Push the [ ] / [ ] button to select 1.Clock “4. Backlight” on the “Initial setting” screen, 2.Name of room then push the “...
Return Note for the Header/follower setting • Set the RBC-AMS51E-ES and RBC-AMS51E-EN remote controller as the Header remote controller when the dual remote controller system is used. • The RBC-AMS51E-ES and RBC-AMS51E-EN remote controller can be used as the Follower remote controller when the dual remote controller system is used that consists of two RBC-AMS51E-ES, RBC-AMS51E-EN remote controllers.
] / [ ] button to select Return a language. Push the [ MENU] button. The screen text changes to the selected language. The factory default is English. These two screens appear for RBC-AMS51E-ES. Language(1/2) English French Français Germany Deutsch Spanish Español Portuguese Português...
Installation Manual Lite-Vision plus Remote Controller 8. Press & hold 4sec. Set the “press and hold” operation for the [ ON / OFF] button. ∧ ∨ Push the [ ] / [ ] button to select Initial setting(2/2) “8. Press & hold 4sec.” on the “Initial 6.Header/Follower setting”...
Installation Manual Lite-Vision plus Remote Controller Field setting menu Push the [ MENU] button to display the menu screen. Field setting menu 1.Test mode 2.Register service info. Push and hold the [ MENU] button and 3.Alarm history ∨ the [ ] button at the same time to 4.Monitor function 5.DN setting...
Page 21
Installation Manual Lite-Vision plus Remote Controller Field setting menu ∧ ∨ Push the [ ] / [ ] button to select 1.Test mode “1. Test Mode” on the “Field setting menu 2.Register service info. screen, then push the “ Set” [ 3.Alarm history 4.Monitor function F2] button.
Installation Manual Lite-Vision plus Remote Controller Using the Service monitor with the [ MONITOR] button during the test mode Room A 12:00 Test Cool Mode Fan Speed Push the [ MONITOR] button Monitor function Code Data 0024 Return Refer to “4. Monitor function” (page 26) for details. When the group control is used, select the unit to monitor in the unit selection screen before displaying the monitoring display.
Page 23
Installation Manual Lite-Vision plus Remote Controller Entering information manually Register service info ∧ ∨ Push the [ ] / [ ] button to select 1.Service contact tel No. “2. Register service info” on the field setting 2.Outdoor model name menu screen. 3.Outdoor unit serial No.
Page 24
Installation Manual Lite-Vision plus Remote Controller Entering the model name and serial number Enter the model name and serial number manually for a Light commercial outdoor unit. Information data is loaded automatically for Light commercial indoor units, VRF indoor units (excluding large capacity air discharge type and duct type), and VRF outdoor units.
Page 25
Installation Manual Lite-Vision plus Remote Controller Outdoor model name ∧ ∨ Push the [ ] / [ ] button to select 1.Manual model name input “1. Manual model name input” on the 2.Model name selection “Outdoor model name” screen, then push Outdoor model name the “...
Installation Manual Lite-Vision plus Remote Controller Checking the model name or serial number The model name or serial number to be displayed on the Outdoor (Indoor) model name or Outdoor (Indoor) unit serial No. screen is displayed. Outdoor model name 1.Manual model name input 2.Model name selection Outdoor model name...
Installation Manual Lite-Vision plus Remote Controller 4. Monitor function The sensor temperature or operational status of indoor unit, outdoor unit, or remote controller can be monitored. Monitor function ∧ ∨ Push the [ ] / [ ] button to select “4.
Installation Manual Lite-Vision plus Remote Controller 5. DN setting Perform the advanced settings for the air conditioner. Carry out the setting operation while the indoor unit is stopped. (Turn off the air conditioning unit before starting the setting operation.) DN setting ∧...