Controlling The Monitor With A Computer (Rs-232C); Computer Connection; Communication Conditions; Communication Procedure - Sharp PN-80TH5 Operation Manual

Hide thumbs Also See for PN-80TH5:
Table of Contents

Advertisement

Controlling the Monitor with a computer (RS-232C)

You can control this monitor from a computer via RS-232C
(COM port) on the computer.
TIPS
• To control the monitor via RS-232C, set RS-232C/LAN
SELECT to RS-232C.
• You cannot use RS-232C and LAN control simultaneously.

Computer connection

Connect the RS-232C conversion cable (supplied) to the RS-
232C input terminal on the monitor. Connect the RS-232C
conversion cable (supplied) to the COM port (RS-232C port)
on your computer with an RS-232 cable (straight).
Computer
To COM port
RS-232 straight cable
(commercially available)
44
E
RS-232C input terminal
RS-232C conversion
cable (supplied)

Communication conditions

Set the RS-232C communication settings on the computer to
match the monitor's communication settings as follows:
Baud rate
*
Data length
8 bits
Parity bit
None
* Set to the same baud rate as the BAUD RATE setting of
SETUP menu. (Initial setting: 38400 bps)

Communication procedure

nCommand format
When a command is sent from the computer to the monitor,
the monitor operates according to the received command and
sends a response message to the computer.
C1
C2
C3
C4
Command field
(4 prescribed
alphanumerical characters)
Example: VOLM0030
VOLM
30
* Be sure to input 4 characters for the parameter. Pad with
spaces (" ") if necessary.
("
" is a return code (0D
Wrong : VOLM30
Right
: VOLM
30
When inputting a negative value, specify a numerical value in
three digits.
Example: AUTR-005
When the parameter part is 5 or more characters, specify
parameters using a specified number of characters without
using spaces.
Example: MPOS010097
If a command has "R" listed for "Direction" in the
"RS-232C command table" on page 47, the current value can
be returned by using "?" as the parameter.
Example:
VOLM ? ? ? ?
30
Stop bit
1 bit
Flow control
None
Return code
P1
P2
P3
P4
Parameter field
(4 character string comprised of:
0-9, +, -, space, ?)
, 0A
or 0D
))
H
H
H
From computer to monitor
(How much is current volume
setting?).
From monitor to computer
(Current volume setting: 30).

Advertisement

Table of Contents
loading

Table of Contents