Trouble shooting 22
OUTDOOR UNIT Error Method:
Outdoor Thermistor Error
Detective Actuators:
Outdoor temperature thermistor
Forecast of Cause:
1. Connector connection failure, open 2. Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics(Rough value)
Temperature
(°C )
Temperature
(°F )
Resistance value (k )
Temperature
(°C )
Temperature
(°F )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Test 3 : Check Voltage of Controller PCB (DC 5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
1
2
2
CN61
BLACK
3
3
If the voltage does not appear, replace Controller PCB and execute the check operation again.
Indicate of Display:
Indoor Unit :
Operation lamp: 7 times Flash,
Timer lamp
ERROR CODE : [E : 74]
Detective details:
When Outdoor temperature thermistor open or short-circuit is detected
at power ON or while running compressor.
-30
-20
-10
-22
-4
14
224.33
115.24
62.28
60
70
80
140
158
176
2.36
1.65
1.65
Outdoor Temp. Thermistor
Outdoor unit :
: 4 times Flash
0
10
20
32
50
68
35.21
20.72
12.64
02-25
PUMP
LOW
POWER
DOWN
NOISE
ERROR
MODE
(L1)
(L2)
(L3)
(L4)
7
4
2
: Light OFF
: Light ON
n : n times blinking
30
40
50
86
104
122
7.97
5.18
3.45
PEAK
CUT
(L5)
(L6)