Fujitsu ASU30RLE Service Instruction page 108

Split type room air conditioner
Hide thumbs Also See for ASU30RLE:
Table of Contents

Advertisement

 Forced thermostat off function
Function
Mode
External input and
setting /
0-1
60-00 / 2
9
60-09 / B
10
60-10 / C
Input
Compressor
• Example of individual connection
Forced thermostat off is one of the function to save energy. For example, case of using ventilator
at condition with outdoor temperature is lower than indoor temperature, indoor unit of air condi-
tioner stop based upon receiving signal from external controller. (Cooling only)
Cooling operation
(Thermostat on)
Indoor
temperature
Rotary SW on
output PCB
External input and
On
Off
On
Off
Room temp.
Set temp.
Direct digital
controller
Thermistor
Ventilator
Thermistor
82˚F
Outdoor
temperature
(28˚C)
88˚F
Office
Fri 10:00AM
Mode
Set Temp.
Fan
80°F
Custom
Cool
(31˚C)
Auto
Heat
74°F
Auto
Cool
84°F
Room Temp.
Away
Heat
68°F
76°F
Vacation
Status
Menu
External input
CN313
output PCB
Fan stop
(Thermostat off)
03-18
Input
Command
signal
Thermostat
Off → On
off
Normal
On → Off
operation
Indoor
Outdoor
temperature
temperature
82˚F
75˚F
(28˚C)
(24˚C)
Office
Fri 10:00AM
Mode
Set Temp.
Fan
Cool
80°F
Custom
Auto
Auto
Heat
74°F
Away
Cool
84°F
Room Temp.
Heat
68°F
76°F
Vacation
Status
Menu

Advertisement

Table of Contents
loading