 Set point attainment status
NOTE: This function is valid only when function setting 96 is set to "01" (Primary unit) or "02"
(Secondary unit).
When the room temperature does not reach the set point at a room due to the lower cooling perfor-
mance caused by external factor such as the outdoor temperature change, signal is output to tell
the attainment status of set point.
Function
Mode
External input and
setting /
12
60-12 / D
Output signal
Off
Reached the set point. (Tr ≤ Tsα +1°F [0.5°C])
Unreached the set point. (Tr > Tsα +5°F [2.5°C])
On
However, even if the set point unreached, the signal will not be output for 7 minutes
after power is turned on.
When performing the server room control, both of the primary unit and secondary unit output the set
point attainment status if any of the unit is outputting alternative operation command.
When starting operation*
Tr ≤ Tsα + 1°F (0.5°C)
*: When starting operation or resetting, judges the zone to descending direction.
Rotary SW on
output PCB
Output of indoor unit
Output: On
Output: Off
External output
CN3
Condition
Tr > Tsα + 5°F (2.5°C)
03-22
Output
Command
signal
On → Off
Normal
Set point
Off → On
attainment