Fujitsu ASU30RLE Service Instruction page 57

Split type room air conditioner
Hide thumbs Also See for ASU30RLE:
Table of Contents

Advertisement

Trouble shooting 18
OUTDOOR UNIT Error Method:
Discharge Thermistor Error
Detective Actuators:
Discharge temperature thermistor
Forecast of Cause:
1. Connector connection failure, open 2. Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics(Rough value)
Temperature
(°C )
Temperature
(°F )
Resistance value (k )
Temperature
(°C )
Temperature
(°F )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Test 3 : Check Voltage of Controller PCB (DC 5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
1
BLACK
2
2
CN62
BLACK
3
3
BLACK
4
4
If the voltage does not appear, replace Controller PCB and execute the check operation again.
Indicate of Display:
Indoor Unit :
Operation lamp: 7 times Flash,
Timer lamp
ERROR CODE : [E : 71]
Detective details:
When Discharge temperature thermistor open or short-circuit is detected
at power ON or while running compressor.
-20
-10
0
-4
14
32
531.56
292.91
168.60 100.91 62.55
70
80
90
158
176
194
8.70
6.27
4.60
Discharge Temp. Thermistor
Compressor Temp. Thermistor
: 1 times Flash
10
20
30
50
68
86
26.34
40.01
100
110
120
212
230
248
3.43
2.60
2.00
02-21
Outdoor unit :
PUMP
LOW
POWER
DOWN
NOISE
ERROR
(L1)
(L2)
(L3)
(L4)
MODE
1
7
2
: Light OFF
: Light ON
n : n times blinking
40
50
60
104
122
140
17.79
12.30
PEAK
CUT
(L5)
(L6)