Fujitsu ASU30RLE Service Instruction page 59

Split type room air conditioner
Hide thumbs Also See for ASU30RLE:
Table of Contents

Advertisement

Trouble shooting 20
OUTDOOR UNIT Error Method:
Heat Ex. Middle Temp.
Thernistor Error
Detective Actuators:
Heat ex. middle temp. thermistor
Forecast of Cause:
1. Connector connection failure, open 2. Thermistor failure 3. Main PCB failure
Test 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Test 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics(Rough value)
Temperature
(°C )
Temperature
(°F )
Resistance value (k )
Temperature
(°C )
Temperature
(°F )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Test 3 : Check Voltage of Controller PCB (DC 5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
1
BLACK
2
2
CN63
3
3
BLACK
4
4
BLACK
5 5
If the voltage does not appear, replace Controller PCB and execute the check operation again.
Indicate of Display:
Indoor Unit :
Operation lamp: 7 times Flash,
Timer lamp
ERROR CODE : [E : 73]
Detective details:
When Heat exchanger middle temperature thermistor open or short-circuit is
detected at power ON or while running compressor.
-30
-20
-10
-22
-4
14
95.58
50.31
27.81
60
70
80
140
158
176
1.19
0.84
0.61
Pipe (Liquid) Temp. Thermistor
Pipe (Mid) Temp. Thermistor
: 3 times Flash
0
10
20
32
50
68
16.05
103.34
9.63
90
194
0.45
02-23
Outdoor unit :
PUMP
LOW
POWER
DOWN
NOISE
ERROR
(L1)
(L2)
(L3)
MODE
13
7
2
: Light OFF
: Light ON
n : n times blinking
30
40
50
86
104
122
3.84
2.53
1.71
PEAK
CUT
(L4)
(L5)
(L6)

Advertisement

Table of Contents