2.1.1
Technical data
Technical data
Number of inputs
Connection technology
Nominal voltage
Signal voltage "0"
Signal voltage "1"
Input filter
Current consumption via K-bus
Switching times
Input current
Electrical isolation
Bit width in process image
Configuration
Use for
Dimensions (W x H x D)
Weight
Permissible ambient temperature
during operation
Permissible ambient temperature
during storage
Permissible relative air humidity
Vibration / shock resistance
EMC immunity / emission
Installation position
Pluggable wiring
Protection class
Approvals/markings
Ex marking
Standard
Marking
ATEX
II 3 G Ex nA IIC T4 Gc
KL17xx/KS17xx
KL1702-0000,
KL1712-0000,
KS1702-0000
KS1712-0000
2
4-wire
120 V
/230 V
120 V
AC
AC
0 V ... 40 V
79 V ... 260 V
80 V ... 140 V
typ. 10 ms
typ. 3 mA
10 ms
> 3 mA, typ. 6 mA
500 V (K-bus / field voltage)
2 input bits
no address or configuration settings required
230 V mains
120 V mains
15 mm x 100 mm x 70 mm (aligned width 12 mm)
app. 60 g
0 °C to +55 °C
-25 °C to +70 °C
5 % ... 95 %, no condensation
according to EN 60068-2-6 / EN60068-2-27, EN 60068-2-29
conforms to EN 61000-6-2 / EN 61000-6-4
Variable
for all KSxxxx terminals
IP20
CE, UKCA,
CE, UKCA, cULus, EAC,
cULus, EAC, GL,
ATEX [} 26]
ATEX [} 26]
Version: 4.1.0
KL1712-0010,
KS1712-0010
24 V
AC/DC
AC/DC
0 V ... 5 V
14 V ... 28.8 V
24 V mains
Product overview
KL1712-0060,
KS1712-0060
60 V
DC
0 V ... 20 V
40 V ... 70 V
Railway mains
CE, UKCA,
cULus, EAC
9