Product overview
2.2.1
Technical data
Technical data
Connection technology
Number of inputs
Nominal voltage
Signal voltage '0'
Signal voltage '1'
Input filter
Input current
Current consumption from K-bus typ. 3 mA
Switching times
Electrical isolation
Bit width in process image
Configuration
Special features
Weight
Permissible ambient temperature
during operation
Permissible ambient temperature
during storage
Permissible relative humidity
Vibration / shock resistance
EMC immunity / emission
Installation position
Protection class
Pluggable wiring
Approvals / markings
12
KL1704, KS1704
2 wire
4
120/230 V
AC
0 V ... 40 V
79 V ... 260 V
typ. 10 ms
4.6 mA typ. at 230 V, 2.3 mA typ. at 120 V
10 ms
500 V (K-bus / field voltage), 3750 V
4 input bits
no address or configuration settings required
resistive/capacitive input behavior
app. 60 g
0°C ... +55°C
-25°C ... +85°C
95 %, no condensation
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
variable
IP20
for all KSxxxx terminals
CE, UKCA, cULus, EAC
Version: 4.1.0
, 1 min.
AC
KL17xx/KS17xx