Download Print this page

Omron G3PA-VD Series Manual page 10

Power solid-state relay

Advertisement

G3PA-(VD)
Note: 1. Replacing Power Device Cartridges
When replacing Power Device Cartridges, use the specified model. Using a Power Device Cartridge other than the specified one
will result in faulty operation and destruction of the elements.
2. Noise Terminal Voltage according to EN55011
Conformance to EN55011 is possible if a capacitor is connected to the load power supply as shown in the diagram below. (G3PA-
VD)
Input
24 VDC
G3PA-VD
Replacement
Note: Be sure to turn OFF the power supply when replacing the Cartridge. Supplying power with the Cartridge removed may result in mal-
function.
G32A-A10-VD/G32A-A20-VD/G32-A420-VD
Use the special tool (provided) to extract the cartridge for replacement with a new one.
Extraction
Follow the procedures below to dismount the Power Device Car-
tridge from the G3PA.
1. Switch off the power.
2. Remove the terminal cover.
3. Hook the indented part of the cartridge with the tool and pull
up on the cartridge to remove it.
Remover
Hook here with
Remover.
Mounting
Follow the procedures below to mount the Power Device Cartridge
on the G3PA.
1. Apply silicone grease (provided with the G32A-A) to the entire
surface of the heat radiator.
2. Make sure that there is no dust or pieces of wire on the heat
radiator of the G32A-A or the G3PA.
Load
240 VAC
Apply silicone grease here.
3. Insert the cartridge into the opening of the G3PA so that the
letters on the cartridge and those on the G3PA are in the same
direction and side A and side B are even.
Side A
4. Attach the terminal cover.
5. Switch on the power and check the G3PA to be sure it works
properly.
G3PA-(VD)
Side B
141

Advertisement

loading