11. Installation

11.2 Selection of the best location

Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unitʼs weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimension "H" is necessary to get a slope to drain as
figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt, The installation parts (and the unit) should be taken
appropriate anti-corrosion measures.
20 _
Fresh Air Intake Unit

Top view

Inspection hole
(unit: mm)
Control box
600

Front view

(unit: mm)
(600X600)
600
Front
H = 20 or more