Indoor unit
8. Electric Characteristics
Model
ARNU07GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU07GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y)
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFA : Indoor Fan Motor
14 _
Ceiling Concealed Duct_Built in (Low Static)
Units
Type
Hz
Volts Voltage Range
B3
B3
B3
50
220-240
B3
B4
B4
B3
B3
B3
60
220
B3
B4
B4
Power Supply
MCA
MFA
1.00
15
1.00
15
Max:264
1.00
15
Min:198
1.00
15
1.20
15
1.20
15
1.00
15
1.00
15
Max:242
1.00
15
Min:198
1.00
15
1.20
15
1.20
15
Note :
1. Voltage range
Units are suitable for use on electrical systems where volt-
age supplied to unit terminals is not below or above listed
range limits,
2. Maximum allowable voltage unbalance between phases is
2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
IFM
Input(W)
kW
FLA
Cooling Heating
0.024
0.76
85
85
0.024
0.76
85
85
0.024
0.76
85
85
0.024
0.76
85
85
115
115
0.038
0.97
115
115
0.038
0.97
0.024
0.76
85
85
0.024
0.76
85
85
0.024
0.76
85
85
85
85
0.024
0.76
115
115
0.038
0.97
115
115
0.038
0.97