LG MULTI V ARNU07GTUA4 Engineering Product Data Book page 177

Hide thumbs Also See for MULTI V ARNU07GTUA4:
Table of Contents

Advertisement

Indoor unit
2. Specifications
Type
Model
Cooling Capacity
Heating Capacity
Casing
Dimensions(WxHxD) Body
Rows x Columns x FPI
Coil
Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)
(High Mode-factory set)
Fan
External Static Pressure mmAq(Pa)
Air Flow Rate(H / M / L)
(Standard Mode)
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
Pipe Connections Gas Side
Drain Pipe(Internal Dia.)
Net Weight
Noise Level(Sound Pressure, 1.5m, H / M / L)
Power Supply
Refrigerant Control
Transmission cable
Notes:
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics" chapter
should be considered for electrical work and design. Especially the power cable and circuit breaker should be
selected in accordance with that.
5. EEV : Electronic Expansion Valve
6. Sound pressure levels are measured at 50Pa External Static Pressure condition.
7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Ceiling Concealed Duct - High Sensible
Unit
ARNU15GBGA4
kW
4.5
kcal/h
3,900
Btu/h
15,400
kW
5
kcal/h
4,300
Btu/h
17,100
Galvanized Steel Plate
mm
1,182 x 298 x 450
inch
46-17/32 x 11-23/32 x 17-23/32
3 x 12 x 21
m
2
0.26
Sirocco Fan
W
350
A
2.65
CMM
13.8 / 11.8 / 8.3
cfm
487 / 417 / 293
8(78)
CMM
13.5 / 12.1 / 9.0
cfm
477 / 427 / 318
6(59)
Direct
BLDC
Mi c roprocessor, Thermostat for cool i n g and heati n g
Foamed polystrene
-
Fuse
mm(inch)
Ø9.52(3/8)
mm(inch)
Ø15.88(5/8)
mm(inch)
25(1)
kg(lbs)
38(83.8)
dB(A)
33 / 32 / 31
1, 220-240, 50
Ø, V, Hz
1, 220, 60
EEV
mm
2
CVV-SB 1.0~1.5 x 2C
Ceiling Concealed Duct (High Sensible)
ARNU18GBRA4
ARNU24GBRA4
5.6
4,800
19,100
6.3
5,400
21,500
Galvanized Steel Plate
Galvanized Steel Plate
1,230 x 590 x 380
1,230 x 590 x 380
48-7/16 x 14-31/32 x 23-7/32
48-7/16 x 14-31/32 x 23-7/32
3 x 16 x 19
0.38
Sirocco Fan
185 x 2
2.4
29.1 / 24.0 / 19.2
34.2 / 29.1 / 24.0
1,027 / 847 / 678
1,208 / 1,027 / 847
8(78)
31.7 / 27.4 / 23.2
35.9 / 31.7 / 27.4
1,119 / 969 / 819
1,269 / 1,119 / 969
6(59)
Direct
BLDC
Mi c roprocessor, Thermost a t f o r cool i n g and heat i n g
Mi c roprocessor, Thermostat for cool i n g and heati n g
Foamed polystrene
Foamed polystrene
-
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25(1)
53(117)
43 / 42 / 41
1, 220-240, 50
1, 220-240, 50
1, 220, 60
EEV
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
l/s = CMM x 1000/60
7.1
6,100
24,200
8.0
6,900
27,300
3 x 16 x 19
0.38
Sirocco Fan
185 x 2
2.40
8(78)
6(59)
Direct
BLDC
-
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25(1)
53(117)
44 / 43 / 42
1, 220, 60
EEV
3
/min x 35.3
_ 3