Electric Characteristics - LG MULTI V ARNU07GTUA4 Engineering Product Data Book

Hide thumbs Also See for MULTI V ARNU07GTUA4:
Table of Contents

Advertisement

Indoor unit

8. Electric Characteristics

Model
Type
ARNU05GSB*4
SB
ARNU07GSB*4
SB
ARNU09GSB*4
SB
ARNU12GSB*4
SB
ARNU15GSB*4
SB
ARNU18GSC*4
SC
ARNU24GSC*4
SC
ARNU30GSVA4
SV
ARNU36GSVA4
SV
ARNU05GSB*4
SB
ARNU07GSB*4
SB
ARNU09GSB*4
SB
ARNU12GSB*4
SB
ARNU15GSB*4
SB
ARNU18GSC*4
SC
ARNU24GSC*4
SC
ARNU30GSVA4
SV
ARNU36GSVA4
SV
Symbols:
MCA :Min, Circuit Amps(A)
MFA:Max. Fuse Amps(see note 5)
kW:Fan Motor Rated Output(kW)
FLA:Full Load Amps(A)
IFM:Indoor Fan Motor
22 _
Wall Mounted Unit (Standard)
Units
Hz
Volts
Voltage range
Max: 264
50
220-240
Min:198
Max: 242
60
220
Min:198
Power supply
MCA
MFA
kW
0.20
15
0.02
0.20
15
0.02
0.20
15
0.02
0.20
15
0.02
0.20
15
0.02
0.36
15
0.08
0.36
15
0.08
1.19
15
0.11
1.19
15
0.11
0.20
15
0.02
0.20
15
0.02
0.20
15
0.02
0.20
15
0.02
0.20
15
0.02
0.36
15
0.08
0.36
15
0.08
1.19
15
0.11
1.19
15
0.11
Note :
1. Voltage range
Units are suitable for use on electrical systems
where voltage supplied to unit terminals is not below
or above the listed range limits.
2. Maximum allowable voltage unbalance between
phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
IFM
Input
FLA
Cooling Heating
0.16
21.0
21.0
0.16
21.0
21.0
0.16
21.0
21.0
0.16
21.0
21.0
0.16
21.0
21.0
0.29
39.5
39.5
0.29
39.5
39.5
0.95
88.0
88.0
0.95
105.0
105.0
0.16
21.0
21.0
0.16
21.0
21.0
0.16
21.0
21.0
0.16
21.0
21.0
0.16
21.0
21.0
0.29
39.5
39.5
0.29
39.5
39.5
0.95
67.0
67.0
0.95
104.0
104.0