CoriolisMaster FCB400, FCH400 CORIOLIS MASS FLOWMETER | CI/FCB400/FCH400-EN REV. H
... 7 Commissioning
... Basic Setup
Menu / parameter
DO 41/42 Freq.
Dig.Out 41/42 Pulse
Dig.Out 51/52 Freq.
FrequencyV3 / V4
Dig.Out 41 / 42 Logic
Dig.Out 51 / 52 Logic
Dig.Out V1 / V2 Logic
Dig.Out V3 / V4 Logic
Qm Max
Qv Max
Density Max
Density Min
Pulses per Unit
Pulse Width
Upper Frequency41 / 42
Upper Frequency51 / 52
Upper FrequencyV3 / V4
System Zero
Description
Selection of process value issued via the frequency or pulse output.
Only if digital output 41 / 42 has been configured as a frequency or pulse output.
Selection of the output function for the relevant binary output.
F / R Signal: The binary output signals the flow direction.
Dual Range: The binary output is activated when measuring range 2 (QmMax 2 / QvMax 2) is selected. This selection is
only available if the parameter 'Range Mode Config' has been configured to Qm or Qv.
Batch End Contact: The binary output is activated when the set fill quantity is reached (only if the FillMass function is
activated).
Only if the relevant digital output has been configured as a binary output.
Sets the upper range value for the mass flow for forward and reverse flow. The value is also used to calculate the
corresponding percentage value.
Setting of the upper measuring range value 1 for the volume flow for feed flow and reverse flow. The value is also used to
calculate the corresponding percentage value.
Sets the maximum / minimum density to be measured. This value is used to calculate the percentage density value. These
parameters are only available if the density output 'Density [unit]' was selected when configuring the power and digital
outputs.
Set pulses per volume or per mass flow unit, and the pulse width for the digital output operating mode 'Pulse'.
Only available if a digital output has been configured as a pulse output, and the volume flow or mass flow has been selected
as the process variable to be output.
Sets the upper range value frequency for the digital output operating mode 'Frequency'. The entered value corresponds to
100 % flow.
Only available if a digital output has been configured as a frequency output, and the volume flow or mass flow has been
selected as the process variable to be output.
Starts the automatic zero point balancing using
Note
Prior to starting the zero point adjustment, make sure that:
There is no flow through the sensor (close all valves, shut-off devices etc.)
The sensor must be filled completely with measuring medium for measurement.
. Automatic zero point balancing takes approx. 60 seconds.