Only when the space heating/cooling is OFF will the heat pump operate to heat domestic water.
DHW PUMP sets whether or not the DHW pump is controlled by the M thermal unit. If the DHW pump is to be controlled
by the M thermal, select YES. If the DHW pump is not to be controlled by the M thermal unit, select NON.
DHW PUMP PRIORITY TIME SET set the operation time of DHW during DHW PRIORITY mode.
dT5_ON sets the temperature difference between the DHW set temperature (T5S) and the DHW tank water temperature
(T5) above which the heat pump providing heated water to the DHW tank. When T5S - T5 ≥ dT5_ON the heat pump
providing heated water to the DHW tank.
Note: When the heat pump's leaving water temperature is
above the DHW mode leaving water temperature operating
limit (T5stop), the heat pump does not provide heated
water to the DHW tank. The DHW mode leaving water
temperature operating limit is related to ambient
temperature as shown in Figure 2-6.3 in Part 2, 6
"Operating Limits".
dT1S5 sets the heat pump's leaving water set temperature
(T1S) relative to DHW tank water temperature (T5). For DHW mode, the user sets the DHW set temperature (T5S) on the
main screen and cannot manually set T1S. T1S is set as T1S = T5 + dT1S5.
Figure 3-7.6 illustrates the operation of the heat pump and
immersion heater(optional) in DHW mode. If the DHW tank
water temperature (T5) is less than the minimum of the DHW
set temperature (T5S) and the heat pump leaving water
temperature operating limit (T5stop) (refer to Figure 2-6.3 in
Part 2, 6 "Operating Limits") less dT5_ON, the heat pump
starts providing heated water to the DHW tank. After
t_TBH_delay minutes have elapsed, the immersion heater is
turned on. If T5 reaches T5stop, the heat pump stops but the
immersion heater continues running until T5 has reached T5S
+ dT5_TBH_OFF
T4DHWMAX sets the ambient temperature above which the heat
pump will not operate in DHW mode. The highest value that
T4DHWMAX can take is 43°C, which is the DHW mode upper ambient
temperature operating limit of the heat pump.
T4DHWMIN sets the ambient temperature below which the heat
pump will not operate in DHW mode. The lowest value that
T4DHWMIN can take is -25°C, which is the DHW mode lower ambient
temperature operating limit of the heat pump.
t_INTERVAL_DHW sets the DHW mode compressor re-start delay. When the compressor stops running, it will not re-start
54
T5
T5S
T5S-dT_ON
Compressor
Abbreviations:
T5: DHW tank water temperature
T5S: DHW set temperature
Abbreviations:
T5: DHW tank water temperature
T5S: DHW set temperature
T5stop: DHW mode leaving water temperature operating limit
TBH: Immersion heater in DHW tank
Midea CAC Confidential
Figure 3-7.5: dT5_ON
OFF
ON
OFF
Figure 3-7.6: DHW mode operation
Figure 3-7.7: T4DHWMAX and T4DHWMIN
Abreviations:
HP: Heat pump
TBH: DWH tank immersion heater
AHS: Additional heating source