Midea M thermal Mono Series Engineering Data page 29

Hide thumbs Also See for M thermal Mono Series:
Table of Contents

Advertisement

M thermal Mono
6 Operating Limits
Notes:
Shaded areas indicate If IBH/AHS setting is valid, only IBH/AHS turns on. If IBH/AHS setting is invalid, only heat pump turns on.
Shaded areas indicate water flow temperature drop or rise interval
Shaded areas indicates heat pump runs If the IBH or AHS setting is valid; no heat pump operation if IBH or AHS setting is invalid
28
Figure 2-6.1: Heating operating limits
Outdoor temperature(℃)
35
30
-10
-25
5 12
25 35
Water flow temperature (℃)
Figure 2-6.2: Cooling operating limits
Outdoor temperature(℃)
46
20
10
-5
5 10
25
Water flow temperature (℃)
Figure 2-6.3: Domestic hot water operating limits
Outdoor temperature(℃)
43
30
-10
-25
5 12
25 35
Water flow temperature (℃)
Midea CAC Confidential
55 60
50
50 60
202005