ation of the unit:
2.5
Cold Climate Installation
In cold climate locations installation should take account of the following
considerations:
Never install the unit at a site where the suction side may be exposed directly
to wind.
To prevent exposure to wind, install a baffle plate on the air discharge side of
the unit.
To prevent exposure to wind, install the unit with its suction side facing the
wall.
In areas of heavy snowfall, a canopy should be installed to prevent snow
entering the unit. Additionally, the height of the base structure should be
increased so as to raise the unit further off the ground and make sure that the
heat exchanger coil is not affected by the snow. Refer to Figure 3-2.4.
Notes:
-
Construct a large canopy.
-
Construct a pedestal
-
Install the unit high enough off the ground to prevent it from being buried in snow
2.6
Hot Climate Installation
As the outdoor temperature is measured via the outdoor ambient temperature sensor, make sure to install the outdoor
unit in the shade, or a canopy should be constructed to avoid direct sunlight. So that it is not influenced by the sun's heat,
otherwise system protection may occur.
2.7
Base Structure
Outdoor unit base structure design should take account of the following considerations:
A solid base prevents excess vibration and noise. Outdoor unit bases should be constructed on solid ground or on
structures of sufficient strength to support the unit's weight.
Bases should be at least 100mm high to provide sufficient drainage and to prevent water ingress into the base of the
unit.
Either steel or concrete bases may be suitable.
Outdoor units should not be installed on supporting structures that could be damaged by water build-in in the event
of a blocked drain.
Fix the unit securely to foundation by means of the Φ10 expansion bolt. It is best to screw in the foundation bolts
until their length is 20 mm from the foundation surface.
202005
Figure 3-2.3: Installation room illustration
Midea CAC Confidential
M thermal Mono
Figure 3-2.4: Snow shielding