T1SetC1 sets the temperature 1 of automatic setting curve for cooling mode.
T1SetC2 sets the temperature 2 of automatic setting curve for cooling mode.
T4C1 sets the ambient temperature 1 of automatic setting curve for cooling mode.
T4C2 sets the ambient temperature 2 of automatic setting curve for cooling mode.
ZONE1 C-EMISSION sets the emission type of zone1 for cooling mode.
ZONE2 C-EMISSION sets the emission type of zone2 for cooling mode.
7.6
HEAT MODE SETTING Menu
MENU > FOR SERVICEMAN > HEAT MODE SETTING
3 HEAT MODE SETTING
3.1 HEAT MODE
3.2 t_T4_FRESH_H
3.3 T4HMAX
3.4 T4HMIN
3.5 dT1SH
ADJUST
In HEAT MODE SETTING the following parameters should be set.
HEAT MODE enables or disables heating mode.
t_T4_FRESH_H sets the refresh time of heating mode climate temperature curve.
T4HMAX sets the ambient temperature above which the heat pump will not
operate in heating mode. The highest value that T4HMAX can take is 35°C,
which is the heating mode upper ambient temperature operating limit of the
heat pump. Refer to Figure 3-7.15.
T4HMIN sets the ambient temperature below which the heat pump will not operate in heating mode. The lowest value
that T4CMIN can take is -25°C, which is the heating mode lower ambient temperature operating limit of the heat pump.
Refer to Figure 3-7.16.
dT1SH sets the temperature difference between the heat pump leaving water
temperature (T1) and the heat pump leaving water set temperature (T1S)
above which the heat pump provides heated water to the space heating
terminals.
202005
Figure 3-7.14: HEAT MODE SETTING menu
1/3
3 HEAT MODE SETTING
YES
3.6 dTSH
2.0HRS
3.7 t_INTERVAL_H
16°C
3.8 T1SetH1
-15°C
3.9 T1SetH2
5°C
3.10 T4H1
ADJUST
Midea CAC Confidential
M thermal Mono
3 HEAT MODE SETTING
2/3
3.11 T4H2
2°C
3.12 ZONE1 H-EMISSION
5MIN
3.13 ZONE2 H-EMISSION
35°C
3.14 t_DELAY_PUMP
28°C
-5°C
ADJUST
Figure 3-7.15: T4HMAX, T4HMIN
Abreviations:
T4: Outdoor ambient temperature
Figure 3-7.16: dTSH
Note:
Only when ROOM TEMP is enabled will this function
be available
3/3
7°C
RAD.
FLH
2MIN
57