ASC 2500 G LE / ASC 3500 G LE
7.6

Editing default values

The AirCon Service Center has preset values for the most important
service tasks. The default values appear automatically when you select
the respective menu.
You can alter the following default values if necessary:
Parameter
Pressure increase test time min.
Vacuum time min.
Leak test min.
PAG oil ml. (additional quantity)
UV tracer ml.
Filling Qt. g.
Print recovery value?
1. In the basic menu, use the cursor keys  or  to select "Other
selections":
2. Press ENTER to confirm.
3. Use the cursor key  to select "Service".
4. Press ENTER to confirm.
5. Enter the password "7388".
6. Use the keypad and the cursor keys to enter the information.
7. Press ENTER to confirm.
8. Press STOP to access the standby menu.
EN
Short selection
Free selection
Other selections
ENTER-OK
Initial start-up
Default value
1
20
4
0
7
500
Yes
89