Lindab WH45P Installation Booklet page 12

Circular series - 500 pa / 300 pa fire damper
Hide thumbs Also See for WH45P:
Table of Contents

Advertisement

Wall opening
A opening must be provided in the wall as indicated in the table and
in the drawing
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
EI 90 S Installation within vertical rigid wall
Wall minimum density 500 kg/m³
EI 120 S Installation within vertical rigid wall
Wall minimum density 500 kg/m³
EI 180 S Installation within vertical rigid wall
Wall minimum density 500 kg/m³
EI 90 S Installation within vertical rigid wall
1.
Rock wool, 100 kg/m³
2.
Plasterboard arch infill, thickness 12,5 mm
3.
Self-drilling screw Ø 3,5 X 45 mm
D
Hole size: see table above
E
Damper protrusion from the wall: see table above
Lp Overlap length between fire damper and duct: see section Dimension
Installations within vertical light wall (plasterboard)
Refer to the section Construction supports characteristics for further
information.
Comply with the minimum distances indicated on section Minimum
distances
Wall opening
A opening must be provided in the wall as indicated in the table and
in the drawing
EI 90 S Installation within vertical light wall (plasterboard)
Wall rock wool density up to 100 kg/
m³ (optional)
EI 120 S Installation within vertical light wall (plasterboard)
Wall rock wool density up to 100 kg/
m³ (optional)
12/16
"D" hole size
Fire resistance classification
Da (Ø + 35) x (Ø + 35)
EI 90 S
a (B+50) x (H+50)
(500 Pa)
(square hole)
From Ø + 25
EI 120 S
to Ø + 580
(500 Pa)
(circular hole)
From Ø + 25
EI 180 S
to Ø + 35
(500 Pa)
(circular hole)
"D" hole size
Fire resistance classification
Da (Ø + 35) x (Ø + 35)
EI 90 S
a (B+50) x (H+50)
(500 Pa)
(square hole)
Da (Ø + 35) x (Ø + 35)
EI 120 S
to (B+580) x (H+580)
(500 Pa)
(square hole)
Filling
Fill the space between the wall and the damper as indicated in the
table and in the drawing.
Damper protrusion from
the wall "E"
[mm]
[mm]
215 + Lp
215 + Lp
190 + Lp
EI 120 S / EI 180 S Installations within vertical rigid wall
1.
Sealing indicated in the table
D
Hole size: see table above
S
Wall minimum thickness: see table above
E
Damper protrusion from the wall: see table above
Lp Overlap length between fire damper and duct: see section Dimension
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
Filling
Fill the space between the wall and the damper as indicated in the
table and in the drawing.
Damper protrusion from
the wall "E"
[mm]
[mm]
215 + Lp
215 + Lp
Wall minimum thickness "S"
[mm]
Rock wool 100 kg/m³
100
with infill plasterboard
(thickness 12.5 mm)
Mortar or plaster putty
100
100
Mortar sealing
Wall minimum thickness "S"
[mm]
Rock wool 100 kg/m³
100
with infill plasterboard
(thickness 12.5 mm)
100
Mortar or plaster putty
Sealing
sealing
Sealing