START­UP OIL SIDE
Fuel selection ­ Start­up
Select the oil operation in order to proceed with start up on the oil side.
MAIN SWITCH
SAL
0
1
0 - OFF
1 - ON
!
KMV contactor: check the air fan motor rotation.
If the rotation if not correct invert the two phases on the power supply.
START UP THE BURNER
The control box starts the pre-purge cycle, the fan motor and the oil motor and opens the air flaps in full open positon.
At the end of pre-purging, the control box drives the servomotors into the igniton positon and starts the igniton transformer.
After a few seconds the control box opens the oil valve and starts the flame. After the flame stabilisaton the control box drives the
servomotor in the low flame.
In case of faulty igniton, the control box switches the burner into safety condition, in such a case you must rearm the burner.
Gradually increase burner output from the low flame to the high flame and set oil servomotor curve in order to have
a stable flame. Refer to LAMTEC manual attacched.
Adjusting the maximum air flow rate
Air and Oil adjustment are accomplished through LAMTEC pa-
rameters setting. Refer to LAMTEC manual attacched.
16
www.ecoflam­burners.com
Firing head setting
The firing head is pre-adjusted at the 50% from the factory. The
setting fully open enables to reach the full power of the burner
and full close to reach the minimum power of the burner.
The optimal position depends on the output that we need to
reach but the default setting shall be modified only when you are
not able to reach the suggested combustion value by adjusting
the air flow in the maximum flame.
+