WORKING DIAGRAMS
mbar
40
30
20
10
MAIOR 700.1
0
2000
4000
2000
4000
200
400
TEST BOILER ­ FLAME DIMENSIONS
FLAME LENGHT LIGHT OIL BURNERS
L (m)
11
10
9
8
7
6
5
4
3
2
0
1000
2000
3000
4000
1000
2000
3000
4000
5000
100
200
300
400
FLAME DIAMETER LIGHT OIL BURNERS
Ø (m)
2
1,8
1,6
1,4
1,2
1
0,8
0,6
0,4
0,2
0
1000
2000
3000
4000
1000
2000
3000
4000
5000
100
200
300
400
420010985900
MAIOR 1200.1
MAIOR 1000.1
6000
8000
6000
8000
10000
600
800
1000
5000
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
11000
12000
500
600
700
800
900
1000
5000
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
11000
12000
500
600
700
800
900
1000
10000
12000
14000
12000
14000
1200
1400
kcal/h
11000
12000
13000
14000
15000
x 1000
kW
13000
14000
15000
16000
17000
kg/h
1100
1200
1300
1400
kcal/h
11000
12000
13000
14000
15000
x 1000
kW
13000
14000
15000
16000
17000
kg/h
1100
1200
1300
1400
Calculation of
burner output
Q F = Burner output (kW)
Q N = Rated boiler output(kW)
η = Boiler efficiency (%)
Q F = Q N x 100
η
Working diagrams
The working diagram shows
burner output as a function of
combustion chamber pressure.
It corresponds to the maximum
values specified by EN 276
measured at the test fire tube.
Boiler efficiency should be
taken into consideration when
selecting the burner.
kW
kcal/h*1000
kg/h
The burner/boiler matching does not pose
any problem if the boiler is CE type-
approved.
If the burner must be combined with a
boiler that has not been CE type-approved
and/or its combustion chamber dimensions
are clearly smaller than those indicated in
diagram, consult the manufacturer.
The firing rates were set in relation to
special test boilers, according to EN 267
regulations.
The sizes are indicative and dipend on
the configuration, to the combustion
chamber pressure and to the draught.
The values have been taken out from
tests executed with flame tubes.
The dimensions of the flame are made
in test boiler in laboratory without
resistence therefore exists max and
min lenght that take into account the
difference in lenght that comes from the
boiler backpressure.
Example:
Burner thermal output = 8000 kW;
L flame (m) = 5 m (medium value)
D flame (m) = 1 m (medium value)
WARNING: Some flame modifications
can be done in our FLEXSHOP in the
factory in order to shape the flame and
adapt it to some special boiler
or application.
www.ecoflam­burners.com