  • Page 1 OIL BURNER MAIOR P 300.1 AB MAIOR P 400.1 AB DRYER HYDRAULIC SYSTEM Three stage 420010374602 26.11.2012...
  • Page 2: Technical Data

    420010374602 Maior P 300.1/400.1 AB TECHNICAL DATA MODELS MAIOR P 300.1 AB MAIOR P 400.1 AB Thermal power max. kcal/h 2.586.000 3.362.000 3.000 3.900 Thermal power min. kcal/h 867.300 1.127.500 1.000 1.300 Max. flow rate light oil kg/h Min. flow rate light oil...
  • Page 3: Burner Installation

    420010374602 Maior P 300.1/400.1 AB BURNER INSTALLATION 1 - BURNER 2 - NUT 3 - WASHER 4 - GASKET 5 - BOLT 6 - BOILER 7 - GASKET HYDRAULIC CIRCUIT SUCTION RETURN HOSE OIL FILTER OIL COCK SUCTION RETURN MAXIMUM LENGTH OF SUCTION LINES FOR TWO-PIPE SYSTEM Two-pipe siphon feed system To correct length of pipes is calculated by summing up the...
  • Page 4 420010374602 Maior P 300.1/400.1 AB NOZZLE FLOW RATE DELAVAN B - MONARCH PLP PUMP PRESSURE (bar) NOZZLE 2,50 9,50 9,97 10,41 10,83 11,24 11,64 12,02 3,00 11,40 11,96 12,49 13,00 13,49 13,96 14,42 3,50 13,30 13,95 14,57 15,17 15,74 16,29 16,83 4,00 15,20...
  • Page 5: Start-Up And Adjustment

    420010374602 Maior P 300.1/400.1 AB PRIMING AND ADJUSTMENT OF OIL PUMP SUNTEC TA2C4 SUNTEC J 7 C 1000 1 - INLET 2 - RETURN 3 - BLEED AND PRESSURE GAUGE PORT 4 - VACUUM GAUGE PORT SUNTEC SUNTEC SUNTEC 5 - PRESSURE ADJUSTMENT 6 - TO NOZZLE VERIFY: - That piping system is perfectly sealed;...
  • Page 6 420010374602 Maior P 300.1/400.1 AB LANDIS LMO 44 CONTROL INFORMATION SYSTEM In case of burner lockout, it is possible to read which cause originated it. Proceed as follows: with the burner in lockout mode (red LED switched on) keep pressed the lockout button for more than 3 sec. then release it. The red LED will blink according to the following error code list: Error Code Possible cause...
  • Page 7 420010374602 Maior P 300.1/400.1 AB COMBUSTION AIR FLOW ADJUSTMENT (HIGH-LOW FLAME) 2nd stage 3rd stage – – Air flow adjustment in Low Flame (1st Stage): 1 – Open thermostats TAB1 and TAB2 (see wiring diagram). 2 – Start the burner (while checking that air damper is partially open). 3 –...
  • Page 8: Electrical Connections

    420010374602 Maior P 300.1/400.1 AB ELECTRICAL CONNECTIONS All burners are factory tested at 400V - 50Hz 3-phase for motors, and 230V - 50Hz single phase with neutral for auxiliary equipments. Should it be necessary to power the burner with 230V - 50Hz, modify the connec- tions on motor and the terminal board as shown in the picture.
  • Page 9 420010374602 Maior P 300.1/400.1 AB pag.9...
  • Page 10 420010374602 Maior P 300.1/400.1 AB pag.10...
  • Page 11 420010374602 Maior P 300.1/400.1 AB MAIOR P 300.1 AB MAIOR P 400.1 AB N° DESCRIPTION code code OIL PUMP SUNTEC J 7CC 1000 65322951 SUNTEC TA2C40105 65322991 COIL SIRAI L159C3 65323770 65323770 OIL VALVE SIRAI L159C3 65323739 65323739 NIPPLE TN 18X1200...
  • Page 12 ECOFLAM BRUCIATORI S.p.A. reserves the right to make any adjustments, without prior notice, which it considers necessary or useful to its products, without affecting their main features. Ecoflam (UK) Limited 12 Goodwood Road , Keytec 7 Business Park, Wyre Road, Pershore, Worcestershire, WR10 2JL England Tel: 01386 556092 - Fax: 01386 553789 Ecoflam Bruciatori S.p.A.