  • Page 1 BRUCIATORI DI GASOLIO OIL BURNERS BRULEURS A MAZOUT QUEMADOR DE GASOLEO MAIOR P 150.1 AB MAIOR P 200.1 AB SISTEMA IDRAULICO HYDRAULIC SYSTEM SYSTEME HYDRAULIQUE SISTEMA HIDRAULICO 420010619500 15.01.2015...
  • Page 2: Working Fields

    420010619500 Maior P 150.1/200.1 AB TECHNICAL DATA MODELS MAIOR P 150.1 AB MAIOR P 200 .1 AB Thermal power max kcal/h 1.530.000 2.040.000 1.780 2.372 Thermal power min. kcal/h 510.000 612.000 Max. flow rate light oil kg/h Min. flow rate light oil...
  • Page 3: Burner Installation

    420010619500 Maior P 150.1/200.1 AB BURNER INSTALLATION 1 - BURNER 2 - NUT 3 - WASHER 4 - GASKET 5 - BOLT 6 - BOILER 7 - GASKET HYDRAULIC CIRCUIT HOSE OIL FILTER OIL COCK SUCTION RETURN MAXIMUM LENGTH OF SUCTION LINES FOR TWO-PIPE SYSTEM Pipe length H (m) Two-pipe siphon feed system...
  • Page 4 420010619500 Maior P 150.1/200.1 AB NOZZLE FLOW RATE DELAVAN B - MONARCH PLP - DANFOSS S PUMP PRESSURE (bar) NOZZLE 2,50 9,50 9,97 10,41 10,83 11,24 11,64 12,02 3,00 11,40 11,96 12,49 13,00 13,49 13,96 14,42 3,50 13,30 13,95 14,57 15,17 15,74 16,29...
  • Page 5 420010619500 Maior P 150.1/200.1 AB 1 - INLET 5 - PRESSURE ADJUSTMENT 2 - RETURN 6 - TO NOZZLE 3 - BLEED AND PRESSURE GAUGE PORT 4 - VACUUM GAUGE PORT VERIFY: - That piping system is perfectly sealed; - That the use of hoses is avoided whenever is possible (use copper pipes preferably); - That depression is not greater than 0,45 bar, to avoid pump’s cavitation;...
  • Page 6 420010619500 Maior P 150.1/200.1 AB SIEMENS LMO 44 CONTROL INFORMATION SYSTEM In case of burner lockout, it is possible to read which cause originated it. Proceed as follows: with the burner in lockout mode (red LED switched on) keep pressed the lockout button for more than 3 sec. then release it. The red LED will blink according to the following error code list: Error Code Possible cause...
  • Page 7: Electrical Connections

    420010619500 Maior P 150.1/200.1 AB ELECTRICAL CONNECTIONS All burners are factory tested at 400V - 50Hz 3-phase for motors, and 230V - 50Hz single phase with neutral for auxi- liary equipments. Should it be necessary to power the burner with 230V - 50Hz, modify the connections on motor and the terminal board as shown in the picture.
  • Page 8 420010619500 Maior P 150.1/200.1 AB pag.26...