15. Protection Control

15.1 Protection Control for All Operations

15.1.1
Restart Control (Time Delay Safety Control)
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
15.1.2
Total Running Current Control
When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for
3 minutes.
Model
Cooling / Soft Dry (X)
Heating (X)
Y
The first 30 minutes of cooling operation, (A) will be applied.
15.1.3
IPM (Power transistor) Prevention Control
Overheating Prevention Control
When the IPM temperature rises to 120.0°C (Z20 ~ 71VK) & 110.0°C (Z80VK), compressor operation will
o
stop immediately.
Compressor operation restarts after 3 minutes the temperature decreases to 110.0°C (Z20 ~ 71VK) & 95.0°C
o
(Z80VK).
If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking ("F96" is indicated).
o
DC Peak Current Control
When electric current to IPM exceeds set value of 18.5 A (Z20 ~ 35VK) and 30.0 ± 5.0A (Z42 ~ 80VK), the
o
compressor will stop operate. Then, operation will restart after 3 minutes.
If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will
o
restart after 1 minute.
If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after
o
1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer
LED will be blinking ("F99" is indicated).
Z20VK
Z25VK
A
3.81
5.52
B
3.37
5.52
C
3.37
5.52
4.33
5.52
15.03
14.66
43.0°C
39.0°C
Outdoor air temperature
Z35VK
Z42VK
Z50VK
6.34
10.32
11.50
5.88
10.32
11.50
5.88
10.32
11.50
6.34
10.32
11.50
14.66
19.01
19.01
(C)
42.0°C
(B)
38.0°C
(A)
104
Z60VK
Z71VK
Z80VK
12.58
14.57
14.38
12.58
12.67
12.18
12.58
12.67
12.18
12.58
14.57
14.99
19.01
19.01
19.01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents