NI cRIO-9066 Getting Started Manual page 7

Embedded real-time controller with reconfigurable fpga
Hide thumbs Also See for cRIO-9066:
Table of Contents

Advertisement

Connecting the cRIO-9066 to Power
The cRIO-9066 requires a 9 V to 30 V external power supply. The cRIO-9066 filters and
regulates the supplied power and provides power for the C Series modules. The cRIO-9066
has one layer of reverse-voltage protection.
The following table lists the POWER LED indicators.
LED Color LED Pattern
Green
Solid
Off
What to Use
Screwdriver, 2.54 mm (0.10 in.) flathead
Power supply, 9 V to 30 V, 25 W maximum
NI recommends the power supply listed in the following table for the cRIO-9066.
NI PS-15 Industrial Power Supply
(24 VDC, 5 A, 100 VAC to 120 VAC/200 VAC to 240 VAC input)
What to Do
Complete the following steps to connect a power supply to the cRIO-9066.
1.
Ensure that your power supply is powered off.
2.
Remove the power connector from the cRIO-9066.
Caution
while the cRIO-9066 is powered on.
3.
Connect the power supply to the power connector, as shown in the following figure.
Table 2. POWER LED Indicators
The cRIO-9066 is powered on and the connected power supply is
adequate.
The cRIO-9066 is powered off.
Table 3. NI Power Supplies
Power Supply
Do not tighten or loosen the terminal screws on the power connector
NI cRIO-9066 Getting Started Guide | © National Instruments | 7
Indication
Part Number
781093-01

Advertisement

Table of Contents
loading

Table of Contents