5.6

Positioning probe - electrode

Before fixing the burner to the boiler, check from
the opening of the blast tube that the probe and
the electrode are correctly positioned, as in
WARNING
Fig. 16.
If, in the previous check, the position of the probe or electrode
was not correct, is necessary:
 remove the screw 1)(Fig. 15)
 extract the inner part 2)(Fig. 15) of the head, and adjust
them.
Do not rotate the probe: leave it as in Fig. 16.
If it is located too close to the ignition electrode,
the control box amplifier may be damaged.
WARNING
Observe the dimensions shown in Fig. 16.
WARNING
Probe
D1209
Installation
1
3
2
Electrode
23
GB
D8150
Fig. 15
Fig. 16
20068446