Contents Information and general warnings............................3 Information about the instruction manual ........................3 1.1.1 Introduction.................................. 3 1.1.2 General dangers................................3 1.1.3 Other symbols ................................3 1.1.4 Delivery of the system and the instruction manual...................... 4 Guarantee and responsibility............................4 Safety and prevention................................5 Introduction..................................
Page 4
Contents Final calibration of the pressure switches ........................31 5.5.1 Air pressure switch..............................31 5.5.2 Maximum gas pressure switch...........................31 5.5.3 Minimum gas pressure switch............................32 5.5.4 PVP pressure switch kit .............................32 Visualisation and programming mode........................33 5.6.1 Normal mode ................................33 5.6.2 Info mode ...................................34 5.6.3 Service mode ................................35 5.6.4...
Information and general warnings Information and general warnings Information about the instruction manual 1.1.1 Introduction WARNING: MOVING PARTS The instruction manual supplied with the burner: This symbol indicates that you must keep limbs is an integral and essential part of the product and must not away from moving mechanical parts;...
Information and general warnings 1.1.4 Delivery of the system and the instruction The system supplier must carefully inform the user about: – the use of the system; manual – any further tests that may be required before activating the When the system is delivered, it is important that: system;...
Safety and prevention Safety and prevention Introduction The burners have been designed and built in compliance with the type and pressure of the fuel, the voltage and frequency of the current regulations and directives, applying the known technical electrical power supply, the minimum and maximum deliveries for rules of safety and envisaging all the potential danger situations.
Technical description of the burner Technical description of the burner Burner designation Range : Fuel : Natural gas Light oil Light oil / Natural gas Heavy oil Size Adjustment : Electronic cam Electronic cam and variable speed (with Inverter) Mechanical cam Proportional air/gas valve Emission : Class 1 EN676...
Technical description of the burner Maximum dimensions The dimensions of the burner are shown in Fig. 1. The dimensions of the open burner are indicated by position H. Bear in mind that inspection of the combustion head requires the burner to be opened and the rear part drawn back on the guides. D495 Fig.
Technical description of the burner 3.7.1 Firing rate on basis of air density If H3 is greater than H1)(Fig. 3), the burner can produce the de- livery requested. The firing rate of the burner shown in the manual is valid for a If H3 is less than H1, it is necessary to reduce the output of the room temperature of 20°C and an altitude of 0m above sea level burner.
Technical description of the burner Test boiler The firing rates were obtained in special test boilers, according to The coupling is ensured when the boiler is EC type-approved; for EN 676 regulations. boilers or ovens with combustion chambers of very different di- mensions compared to those shown in the diagram of Fig.
Technical description of the burner 3.10 Burner description View from A 23 17 D8741 Fig. 5 Combustion head Ignition electrode Screw for combustion head adjustment Pipe coupling Gas servomotor Plug-socket on ionisation probe cable Motor relay 1-0 Operation on/off switch Terminal board for electrical wiring 10 Operator panel with LCD display 11 Control box for checking flame and air/fuel ratio...
To avoid accidents, material or environmental damage, observe the following instructions! The control box is a safety device! Avoid opening WARNING or modifying it, or forcing its operation. Riello S.p.A. cannot assume any responsibility for dam- age resulting from unauthorised interventions! Risk of explosion!
Page 15
Technical description of the burner Electrical connection of flame detector The grounding of the burner must be in compliance with the rules in force; the grounding of the boiler alone is not It is important for signal transmission to be almost totally free enough.
Page 16
Technical description of the burner Cable lengths – Main line AC 230 V Max. 100 m (100 pF / m) – Display, BCI For installation under the casing of the burner or in the control panel max. 3 m (100 pF / m) –...
Technical description of the burner 3.12 Operation sequence of the burner Operation Checking of Start up Shutdown seal TSA1 Phase number Timer - Resolution - Ratio 0.6s Timer 1 (parameters) Timer 2 (parameters) Timer 3 = max. phase time RAST plug Input signals PIN number Thermostat/pressure switch...
Technical description of the burner 3.12.1 List of phases Phase Description Phase Description Ph44 t44 = interval time 1 Ph00 Lockout phase Ph60 Operation Ph02 Safety phase Ph62 The burner moves to the switching off position Ph10 Closing paused Ph70 t13 = post-combustion time Ph12 Standby...
Technical description of the burner 3.13.2 Buttons description Button Button Function To regulate the fuel servomotor Button F (keep pressed and adjust the value by pressing To regulate the servomotor air Button A (keep pressed and adjust the value by pressing To modify the parameter for setting the P mode Button A and F VSD Function...
Technical description of the burner 3.14 Servomotors (SQN13...) Introduction The servomotors that equip the burners of the RS range work di- rectly on the air damper and the gas butterfly valve, without me- chanical leverages but via the interposition of an elastic coupling. They are commanded by the control box, which constantly checks their position by means of a return signal from the optic sensor inside the servomotor.
Installation Installation Notes on safety for the installation After carefully cleaning all around the area where the burner will The installation of the burner must be carried out be installed, and arranging the correct lighting of the environ- by qualified personnel, as indicated in this manual ment, proceed with the installation operations.
Installation Operating position The burner is designed to operate only in Any other position could compromise the cor- positions 1 , 2 , 3 and 4 (Fig. 12). rect operation of the appliance. Installation 1 is preferable, as it is the only ...
Installation Positioning probe - electrode Before fixing the burner to the boiler, check from the opening of the blast tube that the probe and the electrode are correctly positioned, as in Fig. 15. WARNING If, in the previous check, the position of the probe or electrode was not correct, is necessary: ...
Installation Securing the burner to the boiler disconnect the probe and electrode cables and remove the entire burner from the guides, after having removed the split Provide an adequate lifting system of the burner. pin from the guide 5). ...
Installation Central gas adjustment In the central gas regulation two cases are possible: the MINIMUM burner output is lower than 130 kW When the MIN output is between 80 ÷ 129 kW, the ring nut 2)(Fig. 18) value must be adjusted to 0, ir- respective of the MAX burner output.
Installation 4.10 Gas feeding Explosion danger due to fuel leaks in the pres- ence of a flammable source. Precautions: avoid knocking, attrition, sparks and heat. Make sure that the fuel interception tap is closed before performing any operation on the burner. The fuel supply line must be installed by qualified personnel, in compliance with current standards and laws.
Installation 4.10.2 Gas train 4.10.4 Gas pressure Type-approved in accordance with EN 676 and supplied sepa- Tab. L indicates the pressure drop of the combustion head de- rately from the burner. pending on the operating output of the burner. p (mbar) 4.10.3 Gas train installation G 20 G 25...
Page 28
Installation Example with natural gas G 20: Maximum output operation Gas pressure at test point 1)(Fig. 25) 12.7 mbar Pressure in combustion chamber 2.0 mbar 12.7 - 2.0 10.7 mbar A maximum output of 580 kW shown in corresponds to 10.7 mbar pressure.
Installation 4.11 Electrical wiring Notes on safety for the electrical wiring The electrical wiring must be carried out with the electrical supply disconnected. Electrical wiring must be made in accordance with the regulations currently in force in the country of destination and by qualified personnel.
Installation 4.12 Calibration of the thermal relay The thermal relay serves to avoid damage to the motor due to an excessive absorption increase or if a phase is missing. For the calibration, refer to the electrical wiring. – If the motor is star-driven, 400V , the cursor must be posi- tioned on "MIN".
Start-up, calibration and operation of the burner Start-up, calibration and operation of the burner Notes on safety for the first start-up The first start-up of the burner must be carried out Check the correct working of the adjustment, com- by qualified personnel, as indicated in this manual mand and safety devices.
Start-up, calibration and operation of the burner As the burner is not fitted with a device to check the sequence of the phases, the motor rotation may be incorrect. As soon as the burner starts up, go in front of the cooling fan of the fan motor and check it is rotating anticlockwise.
Start-up, calibration and operation of the burner Final calibration of the pressure switches 5.5.1 Air pressure switch Adjust the air pressure switch (Fig. 30) after having performed all other burner adjustments with the air pressure switch set to the start of the scale. With the burner working at MIN output, insert a combustion analyser in the stack, slowly close the suction inlet of the fan (for example, with a piece of cardboard) until the CO value does not...
Start-up, calibration and operation of the burner 5.5.3 Minimum gas pressure switch The purpose of the minimum gas pressure switch is to prevent the burner from operating in an unsuitable way due to too low gas pressure. Adjust the minimum gas pressure switch (Fig. 32) after having adjusted the burner, the gas valves and the gas train stabiliser.
Start-up, calibration and operation of the burner Visualisation and programming mode 5.6.1 Normal mode 5.6.1.4 Condition error message, display of the errors and information The Normal mode is the standard operation mode visualised on the operator panel display. It is the main level of the menu. The display visualises alternately the error code (in the example ...
Start-up, calibration and operation of the burner 5.6.1.5 Reset procedure Releasing the key “ F ” the standard visualisation appears, with the current load percentage flashing: this means that the burner is The burner is in lockout when the red indicator light on the oper- working in Manual mode (any outside adjustment is excluded and ator panel is lit up, and the display visualises the lockout code (in only the safety devices are active).
Start-up, calibration and operation of the burner 5.6.3 Service mode 5.6.4 Parameter mode The Service mode ( SEr ) visualises the error log and certain The Parameters Mode ( PArA ) displays, and allows to be mod- technical information about the system. To access this level you ified/programmed, the list of parameters indicated on page 43.
Start-up, calibration and operation of the burner 5.6.4.2 Allocating the levels of the parameters The password must only be communicated to the The parameters' level is subdivided into groups as shown in Tab. qualified personnel or the Technical Assistance Service, and must be kept in a safe place. WARNING Parameter 100: ParA...
Page 39
Start-up, calibration and operation of the burner 5.7.0.1 Procedure for inserting and adjusting points on Select another point, or exit this area by pressing the keys “+” and “-” ( ESC ) simultaneously. the modulation curve Nine adjustment/calibration points (P1 ÷ P9) can be inserted in the control box for each servomotor, varying their position by de- grees and, consequently, the quantity of air and fuel introduced.
Start-up, calibration and operation of the burner Start-up procedure Check that the operator panel display shows the heat request Otherwise, modify the ignition point, see the section "Procedure and “OFF Upr” : this means it is necessary to set the modulation for inserting and adjusting points on the modulation curve"...
Page 41
Start-up, calibration and operation of the burner The control box will automatically report the same values set at the points “ P0 ” and “ P1 ” to points “ P2 ” to “ P8 ”. The purpose is to reach the point “ P9 ” to adjust/fix the maximum operating power.
Start-up, calibration and operation of the burner Backup / Restore procedure At the end of the "Start-up procedure" it is opportune to make a We suggest carrying out this operation at the end backup, creating a copy of the data memorised on the REC, in of each intervention that modifies what has been the display panel RDI 21.
Start-up, calibration and operation of the burner NOTE: It is advisable to perform a backup every time If an error occurs during the backup process, the display that a parameter is changed, after checking screen shows a negative value. the modification carried out is correct. To determine the cause of the error refer to diagnostic code WARNING 137 (see section "Error codes list"...
Page 44
Start-up, calibration and operation of the burner The value 1 appears on the display screen: h min s After approx 8 seconds (it depends on the duration of the pro- gramme), the 0 value appears on the display screen, this is to in- dicate that the restore process has been completed correctly.
Start-up, calibration and operation of the burner 5.9.3 Parameter list Parameter Value range No. ele- Unit of Modifica- Degree of Default Acces mode ments measure tion accuracy setting Description Min. Max. INTERNAL PARAMETERS Start backup/restore process via RDI21... / PC TOOL (set the parameter to 1) Index 0 = create backup Modification...
Page 46
Start-up, calibration and operation of the burner Parameter Value range No. ele- Unit of Modifica- Degree of Default Acces mode ments measure tion accuracy setting Description Min. Max. Baud Rate for Modbus Values set: Modification Service mode 0 = 9600 1 = 19200 Parity for Modbus 0 = none...
Page 47
Start-up, calibration and operation of the burner Parameter Value range No. ele- Unit of Modifica- Degree of Default Acces mode ments measure tion accuracy setting Description Min. Max. Gas: selection of flame sensor 0 = QRB.../ QRC Modification Service mode 1 = ION / QRA Gas: Selection of the pre-purging function 0 = deactivated...
Page 48
Start-up, calibration and operation of the burner Parameter Value range No. ele- Unit of Modifica- Degree of Default Acces mode ments measure tion accuracy setting Description Min. Max. Position of the fuel servomotor in absence of flame Index 0 = standby position (°) Modification 0°...
Start-up, calibration and operation of the burner Parameter Value range No. ele- Unit of Modifica- Degree of Default Acces mode ments measure tion accuracy setting Description Min. Max. /h, l, h, Actual output Reading only 6553.5 Info mode /h, gal/h Status of external modules and visualisation Reading only Info mode...
Start-up, calibration and operation of the burner 5.14 Final checks (with burner operating) Open the thermostat/pressure switch TL The burner must stop Open the thermostat/pressure switch TS Turn the gas maximum pressure switch knob to the mini- ...
Maintenance Maintenance Notes on safety for the maintenance The periodic maintenance is essential for the good operation, Before carrying out any maintenance, cleaning or checking oper- safety, yield and duration of the burner. ations: It allows you to reduce consumption and polluting emissions and to keep the product in a reliable state over time.
Maintenance Flame inspection window 6.2.4 Safety components Clean the glass of the flame inspection window (Fig. 36). The safety components should be replaced at the end of their life cycle indicated in the following table. The specified life cycles do not refer to the warranty terms indi- cated in the delivery or payment conditions.
Maintenance 6.2.5 Measuring the ionisation current The burner is fitted with an ionisation system to check that a flame is present. The minimum current for control box operation is 4 µA. The Op- erator Panel visualises “30%” (see "Parameter list" at page 43, parameter no.
Maintenance Opening the burner Loosen the screws 1)(Fig. 39) and remove the cover 2). Disconnect the plug 14)(Fig. 16 at page 22) and loosen the Disconnect the electrical supply from the burner grommet 15). by means of the main system switch. ...
Faults - Probable causes - Solutions Faults - Probable causes - Solutions If faults arise in ignition or operations, the burner performs a In the event of a burner lockout, more than two "safety stop", which is signalled by the red burner lockout LED. consecutive burner reset operations could cause The display of the operator panel visualises alternately the lock- damage to the installation.
Page 56
Faults - Probable causes - Solutions Error Diagnostic code Meaning of the REC 27.100A2 system Recommended measures code The valve leak detection is active, but the minimum gas Valve leak detection test not possible pressure switch is selected as input for X9-04 (check parameters 238 and 241) The valve leak detection is active, but no input has been Valve leak detection test not possible...
Page 57
Faults - Probable causes - Solutions Error Diagnostic code Meaning of the REC 27.100A2 system Recommended measures code Carry out a reset; if the error arises repeatedly, replace the 50 ÷ 58 Internal error control box Carry out a reset; if the error arises repeatedly, replace the Internal error: no valid load checking device control box Carry out a reset;...
Page 58
Faults - Probable causes - Solutions Error Diagnostic code Meaning of the REC 27.100A2 system Recommended measures code Overloading of the servomotor or servomotor subjected to mechanical torsion. Bit 4 Deviation of section compared with the last reference 1. Check if the servomotor is blocked in any point along its Valence ...
Page 59
Faults - Probable causes - Solutions Error Diagnostic code Meaning of the REC 27.100A2 system Recommended measures code Insufficient mains voltage. Low level of power supply Conversion of the diagnostic code Voltage value (230 V AC : 1,683) Error code for the carrying out of a reset in the event of power Reset power supply voltage supply restoration (absence of error) Carry out a reset;...
Page 60
Faults - Probable causes - Solutions Error Diagnostic code Meaning of the REC 27.100A2 system Recommended measures code 254 (-2) Interruption owing to transmission error Repeat the reset and backup 255 (-1) Interruption owing to time-out during the restoration Carry out a reset, check the connections and repeat the backup Time-out of the system automation interface Refer to the Modbus User Documentation (A7541) Modbus time-out...
Page 61
Faults - Probable causes - Solutions Error Diagnostic code Meaning of the REC 27.100A2 system Recommended measures code Carry out a reset; if the error arises repeatedly, replace the Internal error control box Carry out a reset; if the error arises repeatedly, replace the Internal error control box Tab.
Page 71
Appendix - Electrical panel layout Wiring layout key Control box for the air/fuel ratio 6 pin plug Operator panel 7 pin plug Filter to protect against radio disturbance Connector for operation without RWF output power regulator kit Burners components Connector for output power regulator kit RWF Boiler components 4 pole socket Output regulator RWF...
Need help?
Do you have a question about the 826 T2 and is the answer not in the manual?
Questions and answers