Electrical connection of flame detector
It is important for signal transmission to be almost totally free
of any disturbances or loss:
always separate the detector cables from the other cables:
– line capacitance reduces the magnitude of the flame sig-
nal.
– Use a separate cable.
Respect the allowed cable lengths.
The ionisation probe is not protected against the risk of elec-
trocution; it must be protected against any accidental con-
tact.
Technical data
Control box
Mains voltage
Mains frequency
Power absorption
Safety class
Load on 'input'
F1 unit fuse (internal)
terminals
Main fuse of perm. network (external)
Undervoltage
–
Safety switch-off from operating position to mains
voltage
–
Restart when mains voltage picks up
Input currents and input voltages
–
UeMax
–
UeMin
–
Iemax
–
IeMin
Voltage detection
–
On
–
Off
Load on 'output'
Total load on the contacts
terminals
–
Mains voltage
–
Total unit input current (safety circuit)
- Fan motor contactor
- Ignition transformer
- Valve
Single contact loading
Fan motor contactor
–
Rated voltage
–
Nominal current
–
Power factor
Alarm output
–
Rated voltage
–
Nominal current
–
Power factor
Ignition transformer
–
Rated voltage
–
Nominal current
–
Power factor
Fuel valve
–
Rated voltage
–
Nominal current
–
Power factor
Display operation
–
Rated voltage
–
Nominal current
–
Power factor
Technical description of the burner
15
GB
The grounding of the burner must be in compliance with the
rules in force; the grounding of the boiler alone is not
enough.
Position the ignition electrode and the ionisation probe so
that the ignition spark cannot form an arc on the probe (risk
of electric overcharge).
AC 230 V -15 % / +10 %
50 / 60 Hz ±6 %
< 30 W (normal)
I, with components in compliance with II and III, ac-
cording to DIN EN 60730-1
6,3 AT
Max. 16 AT
< AC 186 V
> AC 195 V
UN +10%
UN -15%
1.5 mA peak
0.7 mA peak
AC 180...253 V
< AC 80 V
AC 230 V, 50 / 60 Hz
Max. 5 A
AC 230 V, 50 / 60 Hz
2A
cos > 0.4
AC 230 V, 50 / 60 Hz
1A
cos > 0.4
AC 230 V, 50 / 60 Hz
2A
cos > 0.2
AC 230 V, 50 / 60 Hz
2A
cos > 0.4
AC 230 V, 50 / 60 Hz
0,5A
cos > 0.4