NOTE: When installing network wiring, refer to the latest revision of the
wiring diagram(s) appropriate to your specific system configuration,
available from the Downloads | Product Manuals | Wiring Diagrams
section of the Crestron website (www.crestron.com).
NOTE: Do not power up system until all wiring is verified. Care should
be taken to ensure data (Y, Z) and power (24, G) connections are not
crossed.
NOTE: All network wiring must consist of two twisted-pairs. One
twisted pair is the +24V conductor and the GND conductor and the other
twisted pair is the Y conductor and the Z conductor.
NOTE: For larger networks (i.e., greater than 28 network devices), it
may be necessary to add a Cresnet Hub/Repeater (CNXHUB) to maintain
signal quality throughout the network. Also, for networks with lengthy
cable runs or varying types of network devices, it may be desirable to add
a hub/repeater after only 20 network devices.
When calculating the wire gauge for a particular Cresnet run, the length
of the run and the Cresnet power usage of each Cresnet unit to be
connected must be taken into consideration. If Cresnet units are to be
daisy-chained on the run, the Cresnet power usage of each network unit
to be daisy-chained must be added together to determine the Cresnet
power usage of the entire chain. If the unit is a home-run from a Crestron
system power supply network port, the Cresnet power usage of that unit
is the Cresnet power usage of the entire run. The length of the run in feet
and the Cresnet power usage of the run should be used in the following
resistance equation to calculate the value on the right side of the equation.
Resistance Equation
The required wire gauge should be chosen such that the resistance value
is less than the value calculated in the resistance equation. Refer to the
following table.
Operations Guide – DOC. 5857A
40,000
R <
L x P
Wall-Mounted Interface Module
Where:
R = Resistance (refer to the following table).
L = Length of run (or chain) in feet.
P = Cresnet power usage of entire run (or chain).
Wall-Mounted Interface Module: TPS-IMW • 7