Crestron infiNET CLW-SLVS1RF Installation Manual
Crestron infiNET CLW-SLVS1RF Installation Manual

Crestron infiNET CLW-SLVS1RF Installation Manual

Crestron clw-slvs1rf wall box switch: operations guide
Hide thumbs Also See for infiNET CLW-SLVS1RF:

Advertisement

Quick Links

Introduction

Features and Functions

The CLW-SW1RF (-SW1RF) and CLW-SW4RF
(-SW4RF) are stand-alone wall box switches that can also
act as wireless infiNET™ devices that report to a
®
Crestron
control processor through an infiNET gateway
such as the Crestron C2N-MNETGW.
These switches are a part of Crestron's line of lighting
products using infiNET mesh network technology. infiNet
technology is "Wi-Fi" friendly and provides fault
tolerance and increased effective signal strength as
network devices are added.
Up to 30 infiNET devices (including C2N-MNETRPT
infiNET Repeaters) can communicate with one
C2N-MNETGW Gateway. If more devices are needed,
more C2N-MNETGW gateways may be added to a
®
Cresnet
network.
The infiNET switches operate on the 2.4 GHz "ISM
band" (2400 MHz to 2483.6 MHz) at 10 mW. The output
power of these devices allow RF signals to travel
approximately 150 feet indoors and 250 feet outdoors
(subject to site-specific conditions) without the use of
repeaters or other infiNET devices. The range is
dependent on construction of the building, obstructions,
and RF interference from other devices. The location of
the switch is an important factor in determining RF
performance. Adding more infiNET devices or repeaters
to the network effectively increases the range, strength,
and reliability of the network.
The -SW1RF and -SW4RF feature a three-position mode
selection switch. For more information, refer to the latest
version of the infiNET Switches Operations Guide (Doc.
6397) which is available from the Crestron website
(www.crestron.com/manuals). In the absence of control
system communications, the switch can still be used to
control the attached load.
The CLW-SWS1RF (-SWS1RF) and CLW-SWS4RF
(-SWS4RF) are similar to the -SW1RF and -SW4RF
(respectively) with the added capability of working with a
slave unit (CLW-SLVS1RF) in a multi-switch / single
circuit application.
The CLW-SLVS1RF (-SLVS1RF) is a slave unit that
when used in conjunction with the -SWS1RF or the
-SWS4RF acts as an additional switch control point in a
multi-switch / single circuit application. It does not
connect to a Cresnet system and cannot be used without a
-SWS1RF or -SWS4RF. The -SLVS1RF does not have a
mode selection switch. It will emulate the RUN mode of
the -SWS1RF (even if connected to a -SWS4RF) unless
Crestron Electronics, Inc.
15 Volvo Drive Rockleigh, NJ 07647
Tel: 888.CRESTRON
Fax: 201.767.7576
www.crestron.com
infiNET™ SWITCHES
the mode selection switch of the master is set to "OFF".
For more information, refer to the latest version of the
infiNET Switches Operations Guide (Doc. 6397) which is
available from the Crestron website.
These switches are available in white, almond, and black.
White units are designated by part numbers ending in
"W". Almond units are designated by part numbers
ending in "A". Black units are designated by part numbers
ending in "B". Each switch can be covered with a
decorative faceplate (not supplied).

Specifications

Following are specifications for the -SW1RF, -SW4RF,
-SWS1RF, -SWS4RF, and -SLVS1RF.
CLW-SW1RF/-SW4RF, CLW-SWS1RF/-SWS4RF, &
CLS-SLVS1RF Specifications
SPECIFICATION
Power Requirements
Operating Frequency
RF Output Power
Operating Ranges¹
Typical Distance
Indoors
(without repeater)
Typical Distance
Outdoors
Default MNET ID
Switch Type
Load Type
2-Series Control System
2,3
Update File
4
Load Ratings
Incandescent /
Tungsten-Halogen
5
Magnetic Low Voltage
5
Neon / Cold Cathode
(continued on following page)
Installation Guide - DOC. 6293A
DETAILS
Line Power, 120 VAC, 60 Hz
2400 MHz to 2483.6 MHz
(802.15.4 compliant)
10 mW
150 ft
250 ft
(subject to site-specific
conditions)
SW1RF/SW4RF: 01/01
SWS1RF/SWS4RF: 01/01
Single-Pole, Single-Throw
Incandescent, Tungsten-
Halogen, Fluorescent / High
Intensity Discharge (HID),
Electronic Low Voltage,
Magnetic Low Voltage, Neon /
Cold Cathode, Ceiling Fan
Version 3.154 or later
-SW1RF/-SW4RF: 1000W
-SWS1RF/-SWS4RF: 1000W
-SLVS1RF: N/A
-SW1RF/-SW4RF:
1000VA/750W
-SWS1RF/-SWS4RF:
1000VA/750W
-SLVS1RF: N/A
-SW1RF/-SW4RF:
1000VA/750W
-SWS1RF/-SWS4RF:
1000VA/750W
-SLVS1RF: N/A
(2011322)
09.06
Specifications subject to
change without notice.

Advertisement

Table of Contents
loading

Summary of Contents for Crestron infiNET CLW-SLVS1RF

  • Page 1: Features And Functions

    Crestron control processor through an infiNET gateway such as the Crestron C2N-MNETGW. These switches are a part of Crestron’s line of lighting products using infiNET mesh network technology. infiNet technology is “Wi-Fi” friendly and provides fault tolerance and increased effective signal strength as network devices are added.
  • Page 2: Specification

    Refer to the NOTE following these footnotes. Crestron 2-Series control systems include the AV2 and PRO2. Consult the latest Crestron Product Catalog for a complete list of 2-Series control systems. Refer to Derating Charts for Multigang Installations on page 4.
  • Page 3: Industry Compliance

    2.38 in (6.03 cm) 3.81 in (9.68 cm) 3.28 in (8.32 cm) 4.13 in (10.48 cm) Physical view of CLW-SLVS1RF (clockwise from top; Top, Side, and Front) 1.75 in (4.45 cm) 3.81 in (9.68 cm) 3.28 in (8.32 cm) 4.13 in (10.48 cm)
  • Page 4 The load capacity must also be derated. The following charts provide derating information for various applications. 4 • infiNET™ Wall Box Switch : CLW-SW1/4RF, SWS1/4RF, & SLVS1RF Derating Information for Incandescent, Tungsten Halogen, and Electronic Low Voltage Applications Part Number...
  • Page 5: Installation

    3. Push all power wires back into the wallbox and fasten the devices to their respective wallboxes with the provided screws. 4. Attach decorative faceplates. 5. Restore power at the circuit breaker. infiNET™ Wall Box Switch: CLW-SW1/4RF, SWS1/4RF, & SLVS1RF • 5...
  • Page 6 For detailed operating instructions, refer to the latest revision of the infiNET Switches Operations Guide (Doc. 6397) which is available from the Crestron website. Testing a -SW4RF and -SWS4RF With the mode selection switch in the “RUN” position, tap the Button 1 to turn on the load.
  • Page 7: Problem Solving

    CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it was intended, or if it has been subjected to misuse, accidental damage, modification, or improper installation procedures.
  • Page 8: Appendix: Wiring Diagrams

    Figure 2: Adding a Duplex Receptacle Past a Switched Light Fixture Master-Slave Installation Figure 3: Wiring a CLW-SWSXRF (CLW-SWS4RF shown) with a CLW-SLVS1RF 8 • infiNET™ Wall Box Switch : CLW-SW1/4RF, SWS1/4RF, & SLVS1RF Installation Guide - DOC. 6293A...

Table of Contents