Installation; Ckc Pipework - Marstair CX Series Technical Manual

Hide thumbs Also See for CX Series:
Table of Contents

Advertisement

PARTS DESCRIPTION
Envelope containing operating instructions and
Declaration of Conformity
Mounting brackets
Drain Stub/Nut/Gasket
Drain stub adaptor
Screw M5
Washer nylon
Washer M5 shakeproof
Reducing flare nut 1/2" – 3/8"
The unit may be mounted on a wall or solid ceiling using brackets supplied. It should be matched with the appropriately
sized outdoor unit; this instruction should be used in conjunction with the outdoor unit installation instructions.
UNIT COMBINATIONS
Minimum Set Temperature 8°C
INDOOR UNIT
OUTDOOR UNIT
CX(E) 30
CKC 20
CX(E) 40
CKC 30
CX(E) 50
CKC 50
CX(E) 70
CKC 80
CX(E) 90
CKC 90
1.
Fit all kits prior to installing the unit. (Heater kit is easier to fit when unit has been mounted).
2.
Ensure that the mounting surface will support the operating weight of the unit (see table below).
3.
Mark out the mounting positions and drill holes to suit 6mm rawlbolt shields or equivalent strength fasteners
(ensure that the unit is positioned to give sufficient access (min 0.5m) to the removable side panel).
4.
Fix the mounting brackets to the unit in the correct position for wall or ceiling mounting.
5.
Raise the unit into position and secure the fixings,
ensuring that it is square and level.
6.
Remove the drain tray then fit the drain stub, nut &
gasket. Refit the drain tray.
NITROGEN CHARGE
The unit contains a small charge of dry nitrogen, which should
be discharged into the atmosphere. This is a non-toxic, non-
ozone depleting gas with no global warming potential.
FITTING LOSSES, in equivalent straight lengths of pipe (m).
FITTING
45° Bend
90° Bend R/d = 1
90° Bend R/d = 1.5
180° Bend R/d = 1.5
180° Bend C/d = 2.5
90° Elbow
A. USING SUCTION AND LIQUID LINES:
With the expansion device connected to the indoor unit, the equivalent pipe run should be 45m (20m for CKC20) maximum,
including a maximum lift of 7.5m. Fully insulate the suction line. Ensure the suction pipe is insulated well over
the drain tray at the indoor unit. Liquid lines should be routed to avoid hot areas. This prevents flash gas
forming, which may result in erratic control of liquid refrigerant to the evaporator.
MAXIMUM EQUIVALENT LENGTH OF SUCTION LINE PIPE SIZES (m)
SYSTEM
3/8"
CX(E)30 + CKC20
7.5
CX(E)40 + CKC30
-
CX(E)50 + CKC50
-
CX(E)70 + CKC80
-
CX(E)90 + CKC90
-

INSTALLATION

CONTENTS
QTY
Minimum Set Temperature 4°C
INDOOR UNIT
CXE 40
CXE 50
CXE 70
CXE 90
Pipe Size OD
3/8"
1/2"
5/8"
0.12
0.15
0.18
0.37
0.43
0.49
0.24
0.27
0.3
0.73
0.91
1.1
0.46
0.55
0.64
0.67
0.85
1.04
1/2"
5/8"
20
-
15
45
7.5
18
-
11
-
10
1
Pass to the end user.
2
Use to hang unit.
1
Fitted by installer.
1
Convert to ¾" drain if required.
6
To fix brackets to unit.
6
To fix brackets to unit.
6
To fix brackets to unit.
Fit to liquid connection on the CXE 70 indoor unit
1
when matched with a CKC 60 outdoor unit
OUTDOOR UNIT
CKC 20
CKC 40
CKC 60
CKC 80
To calculate the total equivalent
length, the equivalent lengths of all
3/4"
7/8"
fittings in a pipe run must be added
0.21
0.24
to the actual length of pipe in the
0.55
0.61
run: these are the fittings most
likely to be used.
0.37
0.43
1.28
1.46
R = Radius of bend
0.76
0.85
d = Diameter of tube
1.25
1.46
C = Centres of bend
3/4"
7/8"
-
-
-
-
45
-
30
45
25
45
8/19
ACTION
LIQUID LINE (m)
1/4"
3/8"
20
-
-
45
-
20
-
20
-
-
55908061-01
1/2"
5/8"
-
-
-
-
45
-
45
-
20
45