MOUNTING
Whether floor or wall mounted, it is essential that the mounting surface is capable of supporting the unit
weight. Leave space around the unit for air circulation and access for installation and maintenance.
MODEL
A
CKC 20
900
CKC 30
900
CKC 40
900
CKC 50
1000
CKC 60
1000
CKC 80
1000
CKC 90
1000
1.
Individual pipe runs to a maximum of 45m (20m for CKC20), including 7.5m lift, are permissible with
liquid lines. Performance is based on 7.5m pipe runs. Correctly sized pipes for each installation will
result in no significant loss of capacity on extended pipe runs.
a) Pipe sizes are based on:-
Minimum of 3.8 m/s (750 fpm) suction gas velocity for horizontal or downflow.
Minimum of 7.6 m/s (1500 fpm) suction gas velocity for upflow.
Maximum of 15.2 m/s (3000 fpm) suction gas.
b) Where vertical risers exceed 3m, oil traps must be formed in the pipe. This will help ensure that oil
returns to the compressor. Typically fit an oil trap every 3m with a trap at the bottom of the riser.
2.
In calculating equivalent lengths of pipe runs, the effect of bends and fittings must be taken into
account. The table below covers the fittings most likely to be encountered in this installation.
The equivalent lengths of all the fittings in a pipe run should be added together and the total added to
the actual pipe length in order to calculate the total equivalent length.
3.
Use the shortest possible route, avoiding sharp bends.
4.
Completely insulate the suction line, fully over the indoor unit drain tray.
CKC INSTALLATION
Dimensions in mm.
B
C
D
300
560
525
300
560
525
300
560
525
350
660
495
350
660
495
350
660
495
350
760
495
CKC PIPEWORK
16/19
E
F
G
185
60
295
185
60
295
185
60
295
250
60
345
250
60
345
250
60
345
250
70
345
H
275
275
275
325
325
325
325
55908061-01