8.1. MENU TREE.

The MOV has different menus, divided into levels. Level 0 is the initial screen. Level 1 of the menus is accessed
by pressing the corresponding group key (SET, INF, etc). Moving within a given level is done by using the UP and
DOWN arrows. It is possible to go down to levels 2 and 3 by pressing the ENT key. Press CLR to go up a level
within the menu tree. Level 1 for each of the five groups is shown in the following table :
Group
SET
INF
ACT
ENT
Configuration
Unit 7169
GEK-106271

TABLE 6. HMI Menu. Description

Level 1
VIEW PROTECTION
SETTINGS
MODIFY PROTECTION
SETTINGS
• STATUS
• SET DATE/TIME
• COMMUNICATIONS
TRIGGER
• Va- LINE
• Vb- LINE
• Vc- LINE
• V SIDE 1
• V SIDE 2
• DIF ANGLE 521
• DIF FREQUENCY 521
• DIF ANGLE 520
• DIF FREQUENCY 520
• RELAY STATUS
• ACTIVE TABLE
• LINE 89
• 521 LINE BUSBAR
• 520 LINE BUSBAR
• DATE/TIME
• NET BAUDRATE
• NETWORK STOP BITS
• LOCAL BAUDRATE
• LOCAL STOP BITS
• LOCAL SETTINGS
• REMOTE SETTINGS
• LOCAL OPERATIONS
• REMOTE
OPERATIONS
• UNIT NUMBER
• PASSWORD
• t TIMEOUT
MIV Digital Multifunctional Protective Relay
Description
• View settings
• Modify settings
• Shows the relay status
• Updates the relay date and time
• Oscillography trigger by communications
• Line voltage
• Line voltage
• Line voltage
• Busbar voltage 1
• Busbar voltage 2
• Difference in angle in the side breaker
• Difference in frequency in the side
breaker
• Difference in angle in the central breaker
• Difference in frequency in the central
breaker
• Relay status (In/Out of Service)
• Active settings table
• Line switch status
• Line/Busbar voltage status (dead/live at
both sides of the side breaker)
• Line/Busbar voltage status (dead/live at
both sides of the central breaker)
• Relay date and time
• Communication baudrate in the remote
network
• Stop bits, communication in remote
network
• Local communication baudrate
• Stop bits, local communication
• Local setting changes: permitted / not
permitted
• Remote setting changes: permitted / not
permitted
• Local operation performance: permitted /
not permitted
• Remote operations performance:
permitted / not permitted
• Relay unit number
• Allows to modify the relay password
• Communication failure time