6. ACCEPTANCE TESTS
Group 10:
Group 11:
Group 12:
Group 13:
Group 14:
Group 15:
Group 16:
Group 17:
Group 18:
Group 19:
Group 20:
Group 21:
Group 22:
Group 23:
Group 24:
Group 25:
Group 26:

6.4. INDICATORS

Check that pressing the TARGET RESET button with the relay connected to a power supply, all the indicators light
up.

6.5. POWER SUPPLY

During functional tests, terminals A9 and B9 must be connected to ground
• Configure all outputs as function - G.
• Check that with the relay turned off, all the output contacts, except the SYSTEM READY remain open.
• Power the relay at the minimum voltage and check that all the output contacts, except the SYSTEM READY
are closed, that the relay communicates properly (asking for the model), and that consumption is within the
limits shown in Table 1.
• Repeat the test at the rated and maximum voltage.
40
C5, D5
C6, D6
C7, D7
C8, D8
E1, F1
E2, F2
E3, F3
E4, F4
E5, F5
E6, F6
E7, F7
E8, F8
E9, F9
E10, F10
E11, F11
E12, F12
C3, D3
for safety reasons
Table-1:
Voltage (Vdc)
MIV Digital Multifunctional Protective Relay
Trip 6
Trip 7
Trip 8
Trip 9
Trip 10
Trip 11
Trip 12
Trip 13
Trip 14
Trip 15
Trip 16
Trip 17
Trip 18
Trip 19
Trip 20
Trip 21
System ready
Model "H"
Consumption
(mA)
88
550±25%
250
225±25%
300
205±25%
GEK-106271