Error Codes

Extended Error Codes for Hardware Errors
Error Type
Hex
Equivalent
No Error
X000
General Common
X200
Hardware Error
X201
Hardware-
X300
specific Error
X301
X302
(1) X represents the Don't Care digit. Module hardware error codes are typically presented in their Hex Equivalent by the programming software.
Extended Error Codes for Configuration Errors
(1)
Module
Hex Equivalent
Error Code
Binary
X400
010
X401
010
X402
010
X403
010
X404
010
X405
010
X406
010
X407
010
X408
010
X409
010
X40A
010
X40B
010
X40C
010
Publication 1769-UM020A-EN-P - December 2009
Error codes can help troubleshoot your module.
Module
Extended Error
(1)
Error
Information
Code
Code
Binary
Binary
000
0 0000 0000
001
0 0000 0000
001
0 0000 0001
001
1 0000 0000
001
1 0000 0001
001
1 0000 0010
During system configuration, if you set the fields in the configuration
file to invalid or unsupported values, the module generates a
configuration error and the system controller enters a Fault condition.
The invalid configuration data must be corrected and the program
downloaded again for the system to enter Run mode. You cannot
change module configuration data while the system is in Run mode.
Any changes are ignored by the module, which continues to operate
with its previous configuration.
Extended Error
Error Description
Information Code
Binary
0 0000 0000
General configuration error; reserve bits set to 1
0 0000 0001
Invalid output range selected (channel 0)
0 0000 0010
Invalid output range selected (channel 1)
0 0000 0011
Invalid output range selected (channel 2)
0 0000 0100
Invalid output range selected (channel 3)
0 0000 0101
Invalid output format selected (channel 0)
0 0000 0110
Invalid output format selected (channel 1)
0 0000 0111
Invalid output format selected (channel 2)
0 0000 1000
Invalid output format selected (channel 3)
0 0000 1001
Invalid fault value (channel 0)
0 0000 1010
Invalid fault value (channel 1)
0 0000 1011
Invalid fault value (channel 2)
0 0000 1100
Invalid fault value (channel 3)
Module Diagnostics and Troubleshooting
Error Description
No error
General hardware error; no additional information
Power-up reset state
General hardware error
Microprocessor hardware error
D/A converter communication error