Eaton Cutler-Hammer VCP-W Instructions For Installation, Operation And Maintenance page 41

Vacuum circuit breakers
Table of Contents

Advertisement

I.B. 3A74792H04
6-12 TROUBLESHOOTING CHART
SYMPTOM
Undesirably Closes
Fails To Trip
• No Trip Sound
• Trip Sound
But No Trip
Undesirably Trips
Effective 7/97
INSPECTION AREA
• Control Circuit
• Mechanism
• Control Circuit
• Trip Mechanism
• Trip Mechanism
• Vacuum Interrupter
(One or more welded)
• Control Circuit
• Mechanism
PROBABLE DEFECTS
• Close Circuit
(CS/C Getting Shorted)
• Close Release Latch
(Fails to reset)
• Close Floor Tripper
(Fails to reset)
• Control Power
(Fuse blown or switch off)
• Secondary Disconnect
• Auxiliary Switch
(a contact not making, poor or burned)
• Trip Coil
(Burned or open)
• Terminals and Connections
(Poor or burned or open)
• Trip Clapper
(Jammed)
• Trip Bar, Trip Latch
(Jammed)
• Pole Shaft
(Jammed)
• Operating Rod Assembly
(Broken or pins out)
• Control Power
(CS/T Switch, remains made)
• Trip Coil Clapper
(Not resetting)
• Trip Bar or Trip Latch
(Poor engagement of mating
or worn surfaces)
• Trip Bar Reset Spring
(Loss of torque)