CONDENSATE DRAINAGE

The condensate drain pan located in the heat recovery section is equipped with a drain pipe to
remove condensate from the unit. Connect a U-trap to the drain pipe. The U-trap and the drain pan must
be thermally insulated.
The U-trap height, fig. 7, depends on the pressure inside and outside of the section and must be not
less than H=100 mm, h=50 mm.
Fig. 7. Condensate drainage
DRAIN PIPE
CONNECTING PIPE
VUT 300 (301) EV(K) mini EC
min 3°
U-TRAP
CONNECTING PIPE
min 3°
SEWAGE SYSTEM