6.12

Light oil supply

Explosion danger due to fuel leaks in the
presence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure the fuel shut-off valve is closed before
performing any operation on the burner.
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING
Double-pipe circuit
The burner is equipped with a self-priming pump which is capable
of feeding itself within the limits listed in the table at the side.
The tank higher than the burner A
The distance "P" must not exceed 10 meters in order to avoid
subjecting the pump's seal to excessive strain; the distance "V"
must not exceed 4 meters in order to permit pump self-priming
even when the tank is almost completely empty.
The tank lower than the burner B
Pump depression values higher than 0.45 bar (35 cm Hg) must
not be exceeded because at higher levels gas is released from
the fuel, the pump starts making noise and its working life-span
decreases.
It is good practice to ensure that the return and suction lines enter
the burner from the same height; in this way it will be less proba-
ble that the suction line fails to prime or stops priming.
The loop circuit
A loop circuit consists of a loop of piping departing from and re-
turning to the tank with an auxiliary pump that circulates the fuel
under pressure. A branch connection from the loop goes to feed
the burner. This circuit is extremely useful whenever the burner
pump does not succeed in self-priming because the tank dis-
tance and/or height difference are higher than the values listed in
Tab. H.
Installation
+ H
- H
(m)
10
+ 4.0
51
+ 3.0
45
+ 2.0
39
+ 1.0
32
+ 0.5
29
0
26
- 0.5
23
- 1.0
20
- 2.0
13
- 3.0
7
- 4.0
-
Key
H
=
Pump/foot valve height difference
L
=
Piping length
Ø
=
Inside pipe diameter
1
=
Burner
2
=
Pump
3
=
Filter
4
=
Manual on/off valve
5
=
Suction line
6
=
Foot valve
7
=
Rapid closing manual valve remote controlled (only
Italy)
8
=
On/off solenoid valve (only Italy)
9
=
Return line
10
=
Check valve (only Italy)
19
GB
L (m)
RL 70/M
RL 100/M - 130/M
Ø (mm)
12
14
12
112
150
71
99
150
62
86
150
53
73
144
44
66
132
40
60
120
36
54
108
32
47
96
28
34
71
19
21
46
10
8
21
-
D701
Fig. 19
Ø (mm)
14
16
138
150
122
150
106
150
90
150
82
150
74
137
66
123
58
109
42
81
26
53
10
25
Tab. I