6.11 Combustion head setting

The setting of the combustion head depends exclusively on the
maximum burner delivery at which it will be operating.
Turn screw 4)(Fig. 17) until the notch shown in diagram (Fig. 18)
is level with the front surface of flange 5)(Fig. 17).
Example:
RL 70/M, maximum light oil delivery = 50 kg/h
Diagram (Fig. 18) indicates that for a delivery of 50 kg/h the RL
70/M Model requires the combustion head to be set to approx.
Fig. 17
three notches, as shown in Fig. 17.
D462
Notches no.
D1223
Maximum light oil delivery kg/h
Fig. 18