Preparation Before Installation - Daikin FXUQ71AVEB Installation Manual

Vrv system, 4-way blow ceiling suspended type
Hide thumbs Also See for FXUQ71AVEB:
Table of Contents

Advertisement

CAUTION
• Install the indoor and outdoor units, power supply wiring,
remote controller wiring and transmission wiring at least 1
meter away from televisions or radios to prevent image inter-
ference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufficient to eliminate the noise.)
• Install the indoor unit as far as possible from fluorescent
lamps.
If a wireless remote controller kit is installed, the transmis-
sion distance may be shorter in a room where an electronic
lighting type (inverter or rapid start type) fluorescent lamp
is installed. (NOTE 1)
NOTE
1. Restriction applies to the exposed type lighting but does not
apply to the recessed type.
2. When the air outlet is closed, the space shown with "  "
must have a distance of 30mm or more.
3. For setting the airflow direction of horizontal blade, refer to
the operation manual attached to the indoor unit and
remote controller.
(2) Ceiling height
• This indoor unit can be hung from the ceiling of which
height is up to 3.5m (models 100: up to 4.0m).
• However, if the ceiling height exceeds 2.7m (models 100:
3.2m), it is necessary to set on site from the remote con-
troller. Refer to the section "10. FIELD SETTING AND
TEST OPERATION".
(3) Air discharge direction
Select the air discharge pattern according to the installation
location.
In case of 2-way and 3-way, it is required to set on site from
the remote controller.
For details, see the section "10. FIELD SETTING AND
TEST OPERATION".
(Caution) Since there are some restriction on the piping
connection side, make sure to select the air dis-
charge pattern from the Fig. 3.
The names of air outlet are shown in inscription by the num-
ber of "
" marks on the underside of the air outlet.
(Refer to the Fig. 4)
(4) Use hanging bolts for installation.
Investigate if the installation place can withstand the mass
of the indoor unit and, if necessary, hang the unit with bolts
after it is reinforced by beams etc.
(Refer to the installation pattern paper (11) for the mounting
pitch.)
English
(Discharge pattern) (Views from the ceiling)
4-way discharge
2
3
1
4
2-way discharge (optional blocking material kit 2-way
discharge is required)
2
1
.
The indication "
" shows the refrigerant piping outlet
direction.
: Backward outlet piping
(straight outlet)
For upward outlet piping, any outlet pattern can be selected.
: This indication shows the air discharge direction.
*
For cross-reference of air outlet No. to indication on indoor
unit
Name of air outlet
Air outlet 1
Air outlet 2
Air outlet 3
Air outlet 4
No. of air outlet
4
Indoor unit
4.
PREPARATION BEFORE INSTALLA-
TION
(1) Check the locations of indoor unit hanging bolts, pip-
ing outlet holes, drain piping outlet hole and electric
wirings inlet hole. (The drawing shows the view from
the ceiling.) (Refer to Fig. 5 and Fig. 6)
3-way discharge
2
2
1
3
4
2
4
: Rightward outlet piping
(piping needs to be bent)
Fig. 3
Indication on indoor unit
Indication on
indoor unit
Fig. 4
1
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fxuq100aveb

Table of Contents