CAUTION
CAUTION FOR MENDING THE COVER
• In case the cover for penetrating piping is cut off and used
as wiring penetrating hole, after the wiring connection is
finished, mend the cover.
• Cut the sealing material (Small) (9) into two pieces and
wrap each wiring with each piece.
• Seal the clearance around the wiring with putty and insu-
lating material (field supply).
(If insects and small animals get into the indoor unit, short
circuiting may occur inside the control box.)
• If the low voltage wiring (remote controller wiring, trans-
mission wiring) and the high voltage wiring (power supply
wiring, earth wiring) are brought into the indoor unit from
the same place, they may be affected by electric noise
(outside noise) and cause malfunction or failure.
• Keep the distance of 50mm between the low voltage wir-
ing (remote controller wiring, transmission wiring) and the
high voltage wiring (power supply wiring, earth wiring) at
anywhere outside the indoor unit.
If both the wiring are laid down together, they may be
affected by electric noise (outside noise) and cause mal-
function or failure.
Seal with putty and insulating
material.
Power supply wiring/
earth wiring
WARNING
• When wiring, form the wiring orderly so that the control box
lid can be securely fastened.
If the control box lid is not in place, the wiring may float up
or be sandwiched by the box and the lid and cause electric
shocks or a fire.
8-5 WIRING EXAMPLES
< No.1 system: When 1 remote controller is used for 1
indoor unit >
Power supply
Power supply
220-240V/
220-240V/
220·230V
220·230V
~
~
50Hz/60Hz
50Hz/60Hz
L N
L N
IN/D OUT/D
F1
F2
F1
F2
Outdoor unit
L
N
P1 P2 F1 F2 T1 T2
L
Indoor unit A
Indoor unit B
P1 P2
Remote controller
Fig. 40
(option)
English
Sealing material (Small) (9)
Remote controller/
transmission wiring
Fig. 39
Power supply
220-240V/
220·230V
~
50Hz/60Hz
L N
N
P1 P2 F1 F2 T1 T2
L N
P1 P2 F1 F2 T1 T2
Most
downstream
Indoor unit
P1 P2
P1 P2
Remote controller
Remote controller
(option)
(option)
< No.2 system: When carrying out group control or 2
remote controllers control >
Power supply
Note) It is not needed to set the indoor
220-240V/
220·230V
~
50Hz/60Hz
L N
IN/D OUT/D
F1
F2
F1
F2
Outdoor unit
Indoor
unit B
L
N
P1P2F1 F2 T1 T2
L
N
Indoor
unit A
Case of group
P1P2
control
Remote
controller
(option)
Fig. 41
< No.3 system: When BS unit is used >
Power supply
220-240V/
220·230V
~
Outdoor unit
50Hz/60Hz
L N
L
N
Indoor unit A
Remote controller
Fig. 42
NOTE
• Remote controller wiring and transmission wiring do not have
polarity.
WARNING
Be sure to install an earth leakage circuit breaker.
Failure to do so may cause electric shocks and a fire.
unit address when using group
control. (It is automatically set
when the power is turned on.)
Most
downstream
indoor unit
P1P2F1 F2 T1 T2
L
N
P1P2F1 F2 T1 T2
P1P2
P1P2
Remote
Remote
controller
controller
(option)
For use with
2 remote controllers
BS unit
IN/D
OUT/D
OUT/D
IN/D
F1
F2
F1
F2
F1
F2
F1
F2
P1P2F1 F2 T1 T2
P1P2
(option)
16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fxuq100aveb

Table of Contents