Daikin FXUQ71AVEB Installation Manual

Daikin FXUQ71AVEB Installation Manual

Vrv system, 4-way blow ceiling suspended type
Hide thumbs Also See for FXUQ71AVEB:

Advertisement

SYSTEM
MODELS
(4-Way Blow Ceiling Suspended type)
FXUQ71AVEB
FXUQ100AVEB
CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION.
KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
LESEN SIE DIESE HINWEISE VOR DER INSTALLATION SORGFÄLTIG DURCH.
BEWAHREN SIE DIESE ANLEITUNG AN EINEM LEICHT ZUGÄNGLICHEN ORT FÜR
SPÄTERES NACHSCHLAGEN AUF.
VEUILLEZ LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT L'INSTALLATION.
CONSERVEZ CE MANUEL EN LIEU SÛR POUR POUVOIR VOUS Y REPORTER ULTÉRI-
EUREMENT.
LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA INSTALACIÓN
CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS.
PRIMA DELL'INSTALLAZIONE, LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI.
CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER
RIFERIMENTO FUTURO.
ΔΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟΔΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ
ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙΔΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ ΜΕΛΛΟΝΤΙΚΗ ΑΝΑΦΟΡΑ.
LEES DEZE INSTRUCTIES ZOGVULDIG DOOR VOORDAT MET DE INSTALLATIE WORDT
BEGONNEN.
BEWAAR DEZE HANDLEIDING VOOR TOEKOMSTIG GEBRUIK OP EEN GESCHIKTE
PLAATS ONDER HANDBEREIK.
LEIA ATENTAMENTE ESTAS INSTRUÇÕES ANTES DA INSTALAÇÃO.
MANTENHA ESTE MANUAL NUM LOCAL DE FÁCIL ACESSO PARA CONSULTA.
ПЕРЕД УСТАНОВКОЙ ВНИМАТЕЛЬНО ПРОЧИТАЙТЕ ДАННЫЕ ИНСТРУКЦИИ.
ХРАНИТЕ ДАННОЕ РУКОВОДСТВО В ЛЕГКО ДОСТУПНОМ МЕСТЕ ДЛЯ ЕГО
ПОСЛЕДУЮЩЕГО ИСПОЛЬЗОВАНИЯ.
MONTAJDAN ÖNCE BU YÖNERGELERİ DİKKATLİCE OKUYUN
DAHA SONRA BAKMAK ÜZERE BU KILAVUZU SAKLAYIN
INSTALLATION MANUAL
Air Conditioners
English
Deutsch
Français
Español
Italiano
Ελληνικά
Nederlands
Portugues
Русский

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FXUQ71AVEB and is the answer not in the manual?

Questions and answers

Summary of Contents for Daikin FXUQ71AVEB

  • Page 1 English SYSTEM Air Conditioners Deutsch MODELS Français (4-Way Blow Ceiling Suspended type) FXUQ71AVEB Español FXUQ100AVEB Italiano CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION. Ελληνικά KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE. LESEN SIE DIESE HINWEISE VOR DER INSTALLATION SORGFÄLTIG DURCH.
  • Page 2: Table Of Contents

    FXUQ71AVEB VRV SYSTEM Air Conditioners Installation manual FXUQ100AVEB • Consult your local dealer regarding what to do in case of CONTENTS refrigerant leakage. 1. SAFETY PRECAUTIONS ..........1 When the air conditioner is installed in a small room, it is nec- 2.
  • Page 3: Before Installation

    • Have the customer actually operate the air conditioner while CAUTION looking at the operation manual. • Install drain piping according to this installation manual to Instruct the customer how to operate the air conditioner (par- ensure good drainage, and insulate the piping to prevent ticularly cleaning of the air filters, operation procedures, and condensation.
  • Page 4: Selection Of Installation Location

    2-2 OPTIONAL ACCESSORIES Points of the operation explanation • For this indoor unit, the remote controller is separately In addition to the general usage, since the items in the required. operation manual with the WARNING and CAU- • There are 2 kinds of remote controller; wired type and wire- TION marks are likely to result in human bodily injuries less type.
  • Page 5: Preparation Before Installation

    CAUTION (Discharge pattern) (Views from the ceiling) • Install the indoor and outdoor units, power supply wiring, 4-way discharge 3-way discharge remote controller wiring and transmission wiring at least 1 meter away from televisions or radios to prevent image inter- ference or noise.
  • Page 6 (2) Make holes for hanging bolts, piping outlet, drain pip- ing outlet and electric wiring inlet. (unit [mm]) • Use the installation pattern paper (11) which shows the 835 (hanging bolt pitch) above hole locations. • Determine the locations of hanging bolts, piping outlet, drain piping outlet and electric wiring inlet.
  • Page 7 Hanger Hanger Bend the horizontal blade and pull it out. Hanger Fig. 9 • When carrying the indoor unit, hold it by the hanging metal fit- tings. (Refer to Fig. 9) Claw parts How to block the air outlet for 2-way or 3-way air discharge Turn the horizontal •...
  • Page 8: Installation Of The Indoor Unit

    * If the blocking material is difficult to insert, loosen the left and right screws of the lower decoration panel and insert it. Make Drain pan sure to tighten the loosened screws again after the blocking Lower decoration panel material is fixed. (Refer to Fig. 14) Lower decoration panel Insulation Projected part...
  • Page 9: Refrigerant Piping Work

    • Install the indoor unit leveled. (3) Check the level of the unit from 2 directions (air outlet If the unit is inclined and the drain piping side gets high, it ). (Refer to Fig. 18) may cause malfunction of a float switch and results in water leakage.
  • Page 10 Refrigerant piping can be connected from 3 directions. Table 1 • In case of upward piping, remove the piping penetration Dimension for Piping size Tightening processing Flare shape cover, make holes for penetrating piping by cutting the (mm) torque (N·m) flare A (mm) cover with a cutter such as scissors.
  • Page 11 • After leak test, referring to Fig. 22, insulate both the gas • When carrying out upward and rightward piping, use the and liquid piping connection with the attached joint insu- attached L-shaped piping, and insulate the 2 places of lating material (6) and (7) to prevent the piping from get- connection.
  • Page 12: Drain Piping Work

    NOTE 1. The proper pressure for having nitrogen flow through the piping is approximately 0.02MPa, a pressure that makes one feel like breeze and can be obtained through a pressure Metal clamp (2) reducing valve. (accessory) 2. Do not use flux when brazing refrigerant piping. Use phosphor copper brazing filler metal (BCuP-2: JIS Z 3264/B-Cu93P-710/795: ISO 3677) that does not require flux.
  • Page 13 If drain stagnates in the drain piping, the piping may be If the drain riser is installed inclined, the float switch may clogged. malfunction and cause water leakage. • Install supports at a distance of 1 to 1.5m so that the pip- •...
  • Page 14 (2) After piping is finished, check if the drain flows smoothly. < In case of bending the tip > [When the electric wiring work is finished] Tightened part • Gradually pour 1 liter of water from the air outlet into the drain pan (Fig.
  • Page 15: Electric Wiring Work

    Size Wiring Size 4. When the power supply is turned on, the drain pump Wiring will operate. Check drainage. Vinyl FXUQ71AVEB size and (The drain pump will automatically stop after 10 min- cord with H05VV- length 0.75 - sheath or utes.)
  • Page 16 • If a terminal is over tightened, it may be damaged. • Remote controller wiring, transmission wiring. Refer to the table shown below for tightening torque of terminals. Connect the remote controller wiring to [P1 · P2] and the trans- mission wiring to [F1 ·...
  • Page 17 < No.2 system: When carrying out group control or 2 CAUTION CAUTION FOR MENDING THE COVER remote controllers control > • In case the cover for penetrating piping is cut off and used as wiring penetrating hole, after the wiring connection is Power supply Note) It is not needed to set the indoor finished, mend the cover.
  • Page 18 8-6 FOR CONTROL WITH 2 REMOTE CONTROL- 8-8 FOR REMOTE CONTROL (FORCED OFF OR ON/ LERS (TO CONTROL 1 INDOOR UNIT WITH 2 OFF OPERATION) REMOTE CONTROLLERS) (1) Wiring method and specification • For control with 2 remote controllers, set one remote control- •...
  • Page 19: Mounting Corner Cover · Suction Grille

    MOUNTING CORNER COVER · SUC- • After attaching the suction grille in opposite order mentioned in the clause “4. PREPARATION BEFORE INSTALLATION - TION GRILLE (3)” (Refer to Fig. 47-(1)), hook the strap (a) for preventing For test operation without the corner cover, first refer to the suction grille from falling.
  • Page 20 Mode No. CODE (long life type) CODE Ceiling height (m) FIRST Mode SECOND Setting CODE CODE No. FXUQ71AVEB FXUQ100AVEB Approx. Normal 2500 hrs Standard 2.7 or less 3.2 or less More contami- Approx. High 10 (20) 2.7 - 3.0 3.2 - 3.6...
  • Page 21: Wiring Diagram

    < TEST OPERATION > 11. WIRING DIAGRAM • After cleaning the indoor unit inside and the suction grille, (Refer to Fig. 48) carry out test run according to installation manual attached to CONTROL BOX (NOTE 5) the outdoor unit. • When the remote controller operation lamp flashes, it shows WIRELESS REMOTE CONTROLLER that something is abnormal.
  • Page 22 Fig. 48 English...
  • Page 23 3P177351-7S EM12A004A (1303) HT...