Electrical Data - Bryant 566D User Manual

Commercial air-cooled condensing units with 524a air-handling units
Table of Contents

Advertisement

UNIT
524A-B
V*-PH-Hz
524A-C
208/230-1-60
208/230-3-60
072
460-3-60
575-3-60
208/230-1-60
208/230-3-60
090
460-3-60
575-3-60
208/230-3-60
120
460-3-60
575-3-60
208/230-3-60
150
460-3-60
575-3-60
208/230-3-60
180
460-3-60
575-3-60
208/230-3-60
240
460-3-60
575-3-60
208/230-3-60
300
460-3-60
575-3-60
See Legend and Notes on page 73.

ELECTRICAL DATA

524A-B,C STANDARD MOTORS
FAN MOTOR
VOLTAGE
LIMITS
Hp (kW)
187-253
1.3 (0.97)
187-253
2.4 (1.79)
414-506
2.4 (1.79)
518-632
1.0 (0.75)
187-253
2.4 (1.79)
187-253
2.4 (1.79)
414-506
2.4 (1.79)
518-632
2.0 (1.49)
187-253
2.4 (1.79)
414-506
2.4 (1.79)
518-632
2.0 (1.49)
187-253
2.9 (2.16)
414-506
2.9 (2.16)
518-632
3.0 (2.24)
187-253
3.7 (2.76)
414-506
3.7 (2.76)
518-632
3.0 (2.24)
187-253
5.0 (3.73)
414-506
5.0 (3.73)
518-632
5.0 (3.73)
187-253
7.5 (5.59)
414-506
7.5 (5.59)
518-632
7.5 (5.59)
72
POWER SUPPLY
Minimum Circuit
FLA
Amps
7.6
9.5
5.2
6.5
2.6
3.3
1.4
1.8
11.0
13.8
5.2
6.5
2.6
3.3
2.3
2.9
5.2
6.5
2.6
3.3
2.3
2.9
7.5
9.4
3.4
4.3
3.8
4.8
10.2
12.8
4.8
6.0
3.8
4.8
14.6/12.8
18.3/16.0
6.4
8.0
5.1
6.4
21.5/19.4
26.9/24.3
9.7
12.1
7.8
9.8
MOCP
15
15
15
15
20
15
15
15
15
15
15
15
15
15
20
15
15
30/25
15
15
45/40
20
15

Hide quick links: