1. INSTALLATION — Select equipment to match or to be
slightly less than peak load. This provides better humidity
control, less unit cycling, and less part-load operation.
When selecting vapor line sizes, oil return must be evalu-
ated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor unit
is operating.
Ductwork should be sized according to unit size, not build-
ing load.
To minimize the possibility of air recirculation, avoid the use
of concentric supply/return grilles.
Indoor equipment should be selected at no less than
300 cfm/ton.
OPERATING LIMITS
Maximum Outdoor
Minimum Outdoor Ambient
Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge Superheat
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE — 566D150-240 UNITS
FULL LOAD
UNIT
NO. OF
CAPACITY
566D
CYLINDERS
6
150
4
2*
6
180
4
2*
4
240
2
*Requires field-installed unloader.
LIQUID LINE
UNIT
SIZE (in.)
1
/
2
566D150
5
/
8
1
/
2
566D180
/
5
8
7
/
8
5
/
8
566D240
7
/
8
566E150
1
/
2
/
1
2
566E180
5
/
8
1
/
2
566E240
5
/
8
*Bushings required.
APPLICATION DATA — 566D150-240, 566E150-240
115 F
See Minimum Outdoor-Air
Operating Temperature
table below.
55 F
95 F
25 to 55 F
295 F
60 F
MINIMUM
OUTDOOR-AIR
OPERATING
TEMPERATURE (F)
(%)
With
Base
Low-Ambient
Unit
Control
100
20
67
31
33*
40
100
20
–20
67
33
33*
47
100
15
50
20
REFRIGERANT SPECIALTIES PART NUMBERS
LIQUID LINE
SOLENOID VALVE (LLSV)
200RB7T4M
200RA8T5M
200RB7T4M
200RA8T5M
200RA8T7M
200RA9T5M
200RA9T7M
200RB5T4M Qty 2
200RB5T4M Qty 2
200RB5T5M Qty 2
200RB6T4M Qty 2
200RB6T5M Qty 2
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE — 566E150-240 UNITS
FULL LOAD
UNIT
CAPACITY
566E
(%)
150
180
100/50
240
LIQUID LINE DATA — 566D150-240 UNITS
MAX
UNIT
ALLOW.
566D
150
180
240
NOTE: Data above is for units operating at 45 F saturated suction and
95 F entering air.
LIQUID LINE DATA — 566E150-240 UNITS
MAX
UNIT
ALLOW.
566E
150
180
240
2. REFRIGERANT PIPING — It is recommended that the
refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.
For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.
LLSV
SIGHT
COIL
GLASS
AMG/24V
AMI-1TT4
AMG/24V
AMI-1TT5
AMG/24V
AMI-1TT4
AMG/24V
AMI-1TT5
AMG/24V
AMI-1TT7
AMG/24V
AMI-1TT5
AMG/24V
AMI-1TT7
AMG/24V Qty 2
AMI-1TT4 Qty 2
AMG/24V Qty 2
AMI-1TT4 Qty 2
AMG/24V Qty 2
AMI-1TT5 Qty 2
AMG/24V Qty 2
AMI-1TT5 Qty 2
AMG/24V Qty 2
AMI-1TT5 Qty 2
54
TEMPERATURE (F)
SATURATED COND
TEMPERATURE (F)
Base
Unit
90
50
LIQUID LINE
Max Allow.
Pressure
LIFT
Drop
(ft)
(psi)
67
7
82
87
LIQUID LINE
Max Allow.
Pressure
LIFT
Drop
(ft)
(psi)
60
7
FILTER
DRIER
P502-8757S*
P502-8757S*
P502-8757S*
P502-8757S*
P502-8757S
P502-8757S*
P502-8757S
P502-8304S Qty 2
P502-8304S Qty 2
P502-8304S Qty 2
P502-8307S*
P502-8307S*
MINIMUM
OUTDOOR-AIR
With
Low-Ambient
Control
–20
Max Allow.
Temp
Loss
(°F)
2
Max Allow.
Temp
Loss
(°F)
2
SUCTION LINE
ACCUMULATOR
S-7063
S-7063
S-7721
S-7721
S-7721
S-7721
S-7721
S-7063S* Qty 2
S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2