Electrical Data - Bryant 566D User Manual

Commercial air-cooled condensing units with 524a air-handling units
Table of Contents

Advertisement

NOMINAL
UNIT
VOLTAGE
SIZE
(3-Ph, 60 Hz)
208/230
150
460
575
208/230
566D
180
460
575
208/230
240
460
575
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and
Refrigeration
ICF
— Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW
— Total Fan Motor Input (kilowatts)
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC,
Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA
— Rated Load Amps (compressor)
FACTORY-
UNIT
INSTALLED
SIZE
OPTION
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
150
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
566E
180
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
240
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and
Refrigeration
ICF
— Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW
— Total Fan Motor Input (kilowatts)
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC,
Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA
— Rated Load Amps (compressor)

ELECTRICAL DATA

566D150-240
COMPRESSOR
VOLTAGE
RANGE*
RLA
LRA
Min
Max
187
253
49.3
414
528
22.1
518
660
17.9
187
253
63.6
414
528
29.3
518
660
23.8
187
254
67.9
414
508
34.7
518
632
28.8
566E150-240
VOLTAGE
NOMINAL
COMPRESSOR 1
RANGE*
VOLTAGE
(3 Ph, 60 Hz)
Min
Max
RLA
208/230
187
253
20.7
460
414
528
10.0
575
518
660
8.2
208/230
187
253
32.1
460
414
528
16.4
575
518
660
12.0
208/230
187
253
37.8
460
414
528
19.2
575
518
660
13.8
53
FAN MOTORS (Qty 2)
FLA (ea)
Fan No.
1
2
191
4.3
3.7
80
2.3
1.9
69
1.8
1.8
266
4.3
3.7
120
2.3
1.9
96
1.8
1.8
345
4.3
3.7
173
2.3
1.9
120
1.8
1.8
*Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers' Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
COMPRESSOR 2
LRA
RLA
LRA
156
20.7
156
75
10.0
75
54
8.2
54
195
32.1
195
95
16.4
95
80
12.0
80
239
37.8
239
125
19.2
125
80
13.8
80
*Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers' Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option or a field-
installed accessory and is 115-v, 1ph, 60 Hz.
POWER SUPPLY
kW
MCA
MOCP†
69.6
100
1.41
31.7
50
25.6
40
87.5
125
1.41
40.7
60
33.0
50
93.4
150
1.41
48.1
80
40.1
60
FAN MOTORS
Qty 2)
POWER
SUPPLY
FLA (ea)
Fan No.
kW
1
2
MCA
MOCP†
55.6
70
4.3
3.7
1.41
63.5
80
27.7
35
2.3
1.9
1.41
31.3
40
23.1
30
1.8
1.8
1.41
25.9
30
81.2
100
4.3
3.7
1.41
89.2
100
42.1
50
2.3
1.9
1.41
45.7
60
31.6
40
1.8
1.8
1.41
34.5
40
94.1
125
4.3
3.7
1.41
102.0
150
48.4
60
2.3
1.9
1.41
52.0
70
35.7
45
1.8
1.8
1.41
38.5
50
ICF
199
84
73
274
124
100
353
177
124
ICF
186
194
90
94
67
70
236
244
117
120
97
99
286
294
149
153
98
101